Honewell 5817CB Data Sheet



Related Products

Honeywell 5817CB - Wireless Commercial Sensor
Honeywell 5817CBXT
3-Zone Wireless Commercial Fire/Burg Transmitter w/ Magnet
List Price: $170.00
Our Price: $119.99

Related Categories


Document Transcript

5817CB
WIRELESS COMMERCIAL TRANSMITTER

The 5817CB is a universal contact-monitoring transmitter that can be used with household and commercial fire and burglary-initiating devices such as door/window contacts, motion and glassbreak detectors, sprinkler water flow

switches, tamper switches, post indicator valves, manual pull stations and remote duct detectors. Upon activation, it emits an RF signal to a control panel, sending a burglary or fire alarm to a central station.

FEATURES
• The 5817CB has three unique input loops (zones). • The first loop (primary loop) is supervised and typically used for high-priority alarm reporting such as commercial fire or burglary. • The second loop is the built-in, normally closed reed switch used in conjunction with magnet. • The third loop is another normally closed household burglary loop. All three loops may be used. • A fourth (automatically enrolled) loop contains two tamper switches to protect the 5817CB.

MOUNTING
1. Remove the transmitter cover by inserting the flat blade of a small screwdriver into the pry-off slot at the bottom end of the unit (on the right side closest to the cover’s decorative ribs and twisting). 2. Disengage the supplied mounting plate from the unit by inserting the blade of a small screwdriver into the mounting plate release hole (see Diagram 2) and pushing the locking tab out (see Diagram 1). Slide the mounting plate downward along the case back. Note: For this application, the alignment guide strip along one edge of the mounting plate serves no function and may be broken away, if desired. 3. If concealed wiring is to be used, feed the wires through the concealed wiring entry hole on one corner of the plate (surface wiring is mentioned in step 5 below). 4. Install the mounting plate, with its caseholding posts pointing up, in the location selected as described in the installation instructions. Use the two flat-head screws supplied. Note: To ensure proper operation of the unit’s back tamper (when it is separated from the mountain plate), the screws must be anchored to a wall stud or other solid wood material. 5. Set the DIP switch (after the control panel has enrolled the transmitter’s input ID’s) for the desired primary loop characteristics, as described in the table on the following page.

5817CB
WIRELESS COMMERCIAL TRANSMITTER
Primary Loop Options Table Switch Setting On DIP Switch Position 1 Repeating transmission (every 4 sec.) upon primary loop fault use for high priority alarm, such as fire. Single transmission per primary loop change-of-state 2 3 4

Switch must always be in the on position

Switch must always be in the on position

Switch must always be In the off position

Off

Notes: a. In order for the control panel to enroll the transmitter, the DIP switches must be Set to OFF-ON-ON-OFF (see Diagram 2). b. The auxiliary loops are not affected by the DIP switch settings. Wiring Connections Connect the loop wiring to the unit’s terminals before installing the battery (see Diagram 2). Notes: a. Primary loop 1 is a supervised loop and must have an end-of-line (EOL) resistor (470K ohms, supplied) placed across the sensor. Additionally, for primary loop 1, a contact device may not be installed more than 20 feet from the transmitter. b. If loop 2 is not going to be used, the magnet is not necessary. c. If loop 3 is not going to be used, no connection is needed across its terminals. For UL household burglary and fire installations, the loop 3 contact device (if used) may not be more than 3 feet from the transmitter.

SPECIFICATIONS:
• Dimensions: - 1-9/16"W x 3-1/2"H x 1-3/16"D (40mm x 89mm x 30mm) - Battery 3v Lithium (see BATTERY INSTALLATION AND REPLACEMENT). • UL Listings: - Commercial Fire - Household Fire - Household Burg - Commercial Burg

UL864 UL985 UL1023 UL365, UL609, UL1076, UL1610

MOUNTING PLATE HOLE

CASE HOLDING POSTS

HOLD DOWN

MOUNTING PLATE HOLES

CONCEALED WIRING ENTRY HOLE

LOCKING TAB
5817CB-001-V0

Diagram 1. Mounting Plate

Diagram 2. Transmitter, Cover Removed

Note: For UL commercial and household fire installations, only one initiating device may be connected to this transmitter. For UL commercial burglary installations, multiple initiating devices may be used as long as the devices all service the same function such as door/window contacts, motion or glassbreak detectors. All initiating devices must be located within the same room.

ORDERING
5817CB Wireless Commercial/Household Transmitter Honeywell Security & Custom Electronics Honeywell 2 Corporate Center Drive Suite 100 P.O. Box 9040 Melville, NY 11747 www.honeywell.com

L/5817CB/D August 2007 © 2007 Honeywell International Inc.


Uploaded