Honeywell 4297 Polling Loop Extender - Install Guide Dated 11/13



Related Products

Honeywell 4297 - V-Plex Loop Isolation Extender Module
Honeywell 4297
V-Plex Loop Isolation Extender Module
List Price: $142.00
Our Price: $100.99

Document Transcript


ADEMCO 4297
V-Plex
®
Loop Extender Module
For Use With Control/Communicators Supporting V-Plex
®
Loop Devices

INSTALLATION AND SETUP GUIDE
GENERAL INFORMATION
The ADEMCO 4297 V-Plex
®
loop extender module is an
accessory for use with Ademco control panels that support
V-Plex (polling loop) devices. The 4297 module receives
signals from the control panel via its "input" loop, and then
re-transmits boosted copies of these signals via its
"extension" loop.


The 4297 draws power for its internal circuitry and its
extension loop from a supplementary power supply such as
the control panel’s auxiliary power output.
Also, the 4297 isolates open and short circuit faults
occurring on its extension loop from its input
loop. These characteristics allow the 4297 module to be
used to extend the control panel's polling loop, to provide
additional polling loop current, and to provide

electrically
isolated branch loops.


The 4297 module is fully supervised and causes the control
panel to trigger supervision fault indications for devices
wired to the extension loop when operating power to the
module fails, or when an open or short circuit occurs on the
extension loop. Refer to the control panel's installation
instructions for the type of supervision fault indication
provided.

Important Notes:
*
The 4297
cannot
be used to increase the number of
polling loop zones supported by the control panel.
*
The 4297 is
not
designed to be used in a Class A
wiring configuration.
MOUNTING
For UL burglary and all fire installations:
Mount the 4297 module inside a UL Listed enclosure such as
the control panel's enclosure. Note that the enclosure must
be UL Listed for the desired application; i.e., use an attack-
resistant enclosure with a tamper switch for commercial
burglary applications.
For non-UL certified installations:
Mount the 4297 module directly on a surface using the
slotted holes located on the back of its housing (mounting
screws provided). Feed the wires through the slot on the side
or through the breakout located on the back of the housing.
Affix the connections label provided to the inside of the 4297
module's cover or in the control panel cabinet, if used.
WIRING CONNECTIONS
The 4297 module provides a 9-position terminal block for
making power, earth ground and polling loop connections.
The screw terminal assignments on this terminal block are
described in Figure
1
.
UL NOTE:
Use only 14-22 gauge wire.

ULC

For ULC fire installations, the 4297 can be used to
connect the fire alarm control panel to the Vista fire
transmitter. It is not to be used to connect fire alarm
detectors to the ADEMCO (Vista) fire transmitter.



4297-003-V1
9
8
7
6
5
4
3
2
1
TB1
EXTENSION POLLING LOOP
(CLASS B, STYLE 3)
MAX LINE IMPEDANCE 20

}
}
}
}
INPUT POLLING LOOP
(FROM CONTROL) (CLASS B,
STYLE 3)
12VDC POWER INPUT (FROM
CONTROL PANEL OR A SUP-
PLEMENTAL POWER SUPPLY
LISTED FOR THE APPLICATION)

+


+
(NO CONNECTION)

+
FOR IMPEDANCES BELOW WHICH
GROUND FAULTS WILL BE
ANNUNCIATED, REFER TO THE
"SUMMARY OF CONNECTIONS"
LABEL FOR THE CONTROL PANEL.
NOTES:
1.
3.
2.

ALL CIRCUITS ARE SUPERVISED AND POWER LIMITED.
ELECTRICAL SPECIFICATIONS:
WHEN USING AN EXTERNAL POWER SOURCE, CONNECTIONS MUST
BE MADE TO A UL864/UL1481 REGULATED POWER SUPPLY.
WHEN A SUPPLEMENTARY POWER SUPPLY IS USED, CONNECT IT TO
TERMINALS 1 & 2. CONNECT THE POWER SUPPLY (-) TO AUX POWER (-)
ON THE CONTROL PANEL. USE A CLASS II (POWER LIMITED) SUPPLY.
POLLING LOOP VOLTAGE: 8-11 VDC
INPUT POWER VOLTAGE: 12 VDC
INPUT POWER CURRENT: 180MA
*
*
FOR
CE
INSTALLATIONS
TERMINAL 3 MUST BE
CONNECTED TO
EARTH GROUND
4.
USE ONLY 14-22 GAUGE WIRE.
:400MA (LOOP SHORTED)

Figure 1. 4297 Wiring Connections

Power Supply Connections
The 4297 module can draw power for its internal circuitry
and its extension loop from a supplementary power supply
such as the control panel's auxiliary power output. See
Figure 2.

U
L

All power-limited wiring must be separated from non-power
limited and high-voltage wiring by 1/4" (6.4 mm).

Refer to the control panel installation instructions for
programming / installation requirements.


When Using One 4297
Use one 4297 to extend the polling loop, to provide additional
polling loop current, or to provide an extension loop which is
electrically isolated from the input loop.
Make the connections shown in Figure 3 when only one 4297
module is used. Make sure that the wire run length limits
indicated in Table
1
are not exceeded.

When Using Multiple 4297s
Use multiple 4297s to provide up to eight extension loops
which are electrically isolated from each other, or to provide
more current than one 4297 can supply.
Make the connections shown in Figure 4 when multiple 4297
modules are used. Do not wire 4297 modules in series (i.e.,
do not wire one module’s extension loop to another module’s
input loop). Do not use more than eight 4297 modules in
parallel unless otherwise stated in the control panel's
installation instructions. Make sure that the wire run length
limits indicated are not exceeded.
Important Notes:
* Twisted pair is recommended for all polling loop wire runs.
* If an intercom system is being used, keep the polling loop
wiring as far from the intercom wiring as possible
(minimum 6 inches). If this spacing cannot be achieved, use
shielded wire. Note that use of shielded wire reduces the
maximum permissible polling loop wire run length, as
indicated in Table
1
on page 2
.

- 2 -

9
8
7
6
5
4
3
2
1
TB1
CURRENT DRAW:
• 50 mA + EXTENSION LOOP DRAW
DURING ACTUAL OPERATION.
• INCREASES TO 400 mA WHEN
EXTENTION LOOP SHORTENED
INPUT POLLING LOOP (FROM CONTROL).
WHEN USING SUPPLEMENTARY POWER, ON
COMMERCIAL FIRE PANELS, DO NOT CONNECT
THE INPUT POLLING LOOP GROUND ON TERMINAL 7.
NO CONNECTION
4297
USE CONTROL PANEL’S
AUXILIARY POWER OR USE
A SEPARATE POWER SUPPLY
TAKE CARE TO OBSERVE
POWER SUPPLY RATINGS.

+
SUPPLEMENTARY
POWER SUPPLY
+12VDC
POWER
NOTE
USE A CLASS II (POWER LIMITED) POWER
SUPPLY WHICH IS UL LISTED FOR THE
DESIRED FIRE AND/OR BURGLARY
APPLICATION. FOLLOW THE POWER SUPPLY'S
INSTRUCTIONS REGARDING BACKUP
BATTERY AND AC/BATTERY SUPERVISION
SIGNAL CONNECTIONS THAT APPLY TO THE
DESIRED APPLICATION.
GAUGE LENGTH
#22 100 FT
#20 150 FT
#18 225 FT
#16 375 FT
WIRE RUN LENGTH
MUST NOT EXCEED:
4297-001-V0

Note:
See the Installation & Setup Guide for the control panel being used for specific power and wiring requirements.

Figure 2. Typical Supplementary Power Supply Connections


CONTROL PANEL
INPUT POLLING LOOP
EXTENSION POLLING LOOP
TO
OTHER
RPMS
polling_loop_005-V0
V-PLEX
DEVICE
V-PLEX
DEVICE
V-PLEX
DEVICE
V-PLEX
DEVICE
4297


Figure 3. Connections Using One 4297 Module


CONTROL PANEL
EXTENSION POLLING LOOP #1
4297
4297
INPUT POLLING LOOP
polling_loop-006-V1
EXTENSION POLLING LOOP #2


DO NOT CONNECT 4297 MODULES IN SERIES
(i.e., DO NOT CONNECT ONE MODULE'S EXTENSION
LOOP TO ANOTHER MODULE'S INPUT LOOP.)
DO NOT CONNECT MORE THAN EIGHT
4297 MODULES IN PARALLEL.


V-PLEX
DEVICE
V-PLEX
DEVICE

Figure 4. Typical Connections Using Multiple 4297 Modules

CONFIGURATION GUIDELINES
These guidelines apply to control panels that support V-Plex polling loop devices. Some of these control panels
may have additional limitations; refer to the control panel's Installation & Setup Guide for specific power and
wiring requirements.
Maximum number of devices:


All input loops (combined) = 64 devices max.


All input loops (combined) plus
1
output loop =
11
9 devices max.
Maximum wire length limits:
Refer to Table
1
(at right) for wire length per gauge,
and observe the maximum wire length limits.


No individual wire run can exceed 2400 ft. max.


1
input loop plus
1
output loop (combined) = 4000 ft. max


All input loops (combined) plus
1
output loop = 6400 ft. max
Note:
Reduce wire length by ½ if using unshielded
wire in conduit, or if using shielded wire.
Maximum Current:


All input loops (combined) =
1
28mA maximum current limit.


Each output loop =
1
28mA


Any single wire run = 64mA
Table 1
Wire Gauge

Wire Length

#22

650 ft.

#20

950 ft.

#
1
8

1
500 ft.

#
1
6

2400 ft.

– 3 –

SPECIFICATIONS
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––

Physical:
6-7/
1
6"W x 4-
1
/4"H x
1
-
1
/4"D (
1
63mm x
1
08mm x 32mm)

Electrical:
12V Input Rating:
Input Voltage:
1
2VDC
Input Current: 50mA + Extension loop drain (
1
28mA max)

during normal operation. Increases to 400mA

when extension loop shorted.
Float Voltage:
1
3.65VDC
Standby Time: Exceeds 4 hrs with
1
.2AH or larger battery

Recharge Time: Up to 48 hours
Miscellaneous: PTC thermistor provides reverse battery
connection protection
Extension Polling Loop Rating:
Output Current:

1
28mA max. Do not draw more than

1
28mA on any individual extension loop
wire run.
Maximum line impedance:
20 ohms.
Miscellaneous: Refer to
Table 1,
for limits on polling loop
wire run length. The extension loop is power
limited.



SEE THE CONTROL PANEL'S INSTALLATION INSTRUCTIONS FOR
COMPLETE INFORMATION REGARDING THE LIMITATIONS OF
THE ENTIRE SECURITY SYSTEM.

Regulatory Agency Listings
UL 609
commercial burglary,
UL864
commercial fire,
UL985
household fire, and
UL1023
household burglary.
NFPA-72
Compliant


For the latest warranty information, please go to:
www.honeywell.com/security/hsc/resources/wa



FEDERAL COMMUNICATIONS COMMISSION STATEMENTS
The user shall not make any changes or modifications to the equipment unless authorized by the Installation
Instructions or User's Manual. Unauthorized changes or modifications could void the user's authority to operate the
equipment.
CLASS B DIGITAL DEVICE STATEMENT
This equipment has been tested to FCC requirements and has been found acceptable for use. The FCC requires the
following statement for your information:
This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in strict
accordance with the manufacturer's instructions, may cause interference to radio and television reception. It has been
type tested and found to comply with the limits for a Class B computing device in accordance with the specifications in
Part
1
5 of FCC Rules, which are designed to provide reasonable protection against such interference in a residential
installation. However, there is no guarantee that interference will not occur in a particular installation. If this
equipment does cause interference to radio or television reception, which can be determined by turning the equipment
off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• If using an indoor antenna, have a quality outdoor antenna installed.
• Reorient the receiving antenna until interference is reduced or eliminated.
• Move the radio or television receiver away from the receiver/control.
• Move the antenna leads away from any wire runs to the receiver/control.
• Plug the receiver/control into a different outlet so that it and the radio or television receiver are on different branch
circuits.
• Consult the dealer or an experienced radio/TV technician for help.
INDUSTRY CANADA CLASS B STATEMENT
This Class B digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.
FCC / IC STATEMENT
This device complies with Part
1
5 of the FCC Rules, and RSS2
1
0 of Industry Canada. Operation is subject to the
following two conditions: (
1
) This device may not cause harmful interference, and (2) This device must accept any
interference received, including interference that may cause undesired operation.
Cet appareil est conforme à la partie
1
5 des règles de la FCC & de RSS 2
1
0 des Industries Canada. Son fonctionnement
est soumis aux conditions suivantes: (
1
) Cet appareil ne doit pas causer d’interférences nuisibles. (2) Cet appareil doit
accepter toute interférence reçue y compris les interférences causant une réception indésirable.
ÊN7571V4lŠ

N7571V4 11/13 Rev. A















































2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
Copyright

2009 Honeywell International Inc.

www.honeywell.com/security


Uploaded