Honeywell Lyric Installation Guide - Dated 11/15 Rev B



Related Products

Honeywell Lyric Controller - Encrypted Wireless Security System
Honeywell Lyric Alarm System
Encrypted, HomeKit, Wireless Security System
List Price: $500.00
Our Price: $273.99

Related Categories


Document Transcript

Lyric

TM

Controller

Installation and Reference Guide

Ref: LCP500-L
800-18076

4/15 Rev. B – DRAFT (6/25/15)

Lyric Controller Installation and Reference Guide

RECOMMENDATIONS FOR PROPER PROTECTION
The Following Recommendations for the Location of Fire and Burglary Detection Devices
Help Provide Proper Coverage for the Protected Premises.
Recommendations for Smoke and Heat Detectors
With regard to the number and placement of smoke/heat detectors, we subscribe to the
recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted
below.
• Early warning fire detection is best achieved by the installation of fire detection equipment in all
rooms and areas of the household as follows: For minimum protection a smoke detector should be
installed outside of each separate sleeping area, and on each additional floor of a multi-floor family
living unit, including basements. The installation of smoke detectors in kitchens, attics (finished or
unfinished), or in garages is not normally recommended.
• For additional protection the NFPA recommends that you install heat or smoke detectors in the living
room, dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms,
basements and attached garages.
In addition, we recommend the following:
• Install a smoke detector inside every bedroom where a smoker sleeps.
• Install a smoke detector inside every bedroom where someone sleeps with the door partly or
completely closed. Smoke could be blocked by the closed door. Also, an alarm in the hallway outside
may not wake up the sleeper if the door is closed.
• Install a smoke detector inside bedrooms where electrical appliances (such as portable heaters, air
conditioners or humidifiers) are used.
• Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet (12 meters) long.
• Install smoke detectors in any room where an alarm control is located, or in any room where alarm
control connections to an AC source or phone lines are made. If detectors are not so located, a fire
within the room could prevent the control from reporting a fire or an intrusion.

THIS CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR TEMPORAL
PULSE SOUNDING OF FIRE NOTIFICATION APPLIANCES.
KITCHEN
DINING

BEDROOM BEDROOM

TV ROOM

KITCHEN

DINING

BDRM

LIVING ROOM
BDRM
BEDROOM

BEDROOM

LIVING ROOM

Smoke Detectors for Minimum Protection
Smoke Detectors for Additional Protection
Heat-Activated Detectors

BEDROOM

BEDROOM

TO
BR

BEDROOM
KTCHN

LVNG RM

.

CLOSED
DOOR

GARAGE

BASEMENT
floor_plan-001-V1

Recommendations for Proper Intrusion Protection
• For proper intrusion coverage, sensors should be located at every possible point of entry to a home or
premises. This would include any skylights that may be present, and the upper windows in a multilevel building.
• In addition, we recommend that radio backup be used in a security system. This will ensure that alarm
signals can be sent to the alarm monitoring station in the event that the communications are out of
order (if connected to an alarm monitoring station).

-2-

Lyric Controller Installation and Reference Guide

Table of Contents
System Features ..................................................................................................................................................................................................5
Installing the Control ........................................................................................................................................................................................ 7
Battery Installation ............................................................................................................................................................................................... 7
Battery Selection .......................................................................................................................................................................................... 7
Installing the Rechargeable Backup Battery .................................................................................................................................... 7
Replacing the Rechargeable Backup Battery .................................................................................................................................. 7
Wall Mounting ........................................................................................................................................................................................................8
Desktop Mounting ............................................................................................................................................................................................... 9
Place the Back Plate ................................................................................................................................................................................... 9
Install the Desk Stand ................................................................................................................................................................................ 9
AC Power ............................................................................................................................................................................................................... 10
Wiring Overview ................................................................................................................................................................................................. 10
Make Electrical Connections.................................................................................................................................................................. 10
Communications Modules ................................................................................................................................................................................ 11
Communications Module 24-Hour Standby power ...................................................................................................................... 11
Install and Configure Communications Module ...................................................................................................................................... 11
Installing the Cellular Module ................................................................................................................................................................. 11
Checking Signal Strength ....................................................................................................................................................................... 12
Wireless Zones ................................................................................................................................................................................................... 13
General Information ........................................................................................................................................................................................... 13
Zones ............................................................................................................................................................................................................... 13
Range ............................................................................................................................................................................................................... 13
Transmitters .................................................................................................................................................................................................. 13
House Identification .................................................................................................................................................................................. 13
Transmitter Supervision .......................................................................................................................................................................... 13
Transmitter Input Types .......................................................................................................................................................................... 13
Transmitter Battery Life .......................................................................................................................................................................... 13
5800 Series Transmitter Loop Numbers .......................................................................................................................................... 14
Mechanics of Programming ......................................................................................................................................................................... 15
Navigating Menus ............................................................................................................................................................................................... 15
Touch-screen Display ............................................................................................................................................................................... 15
Navigation Keys .......................................................................................................................................................................................... 16
Home Screen ................................................................................................................................................................................................ 16
Security Screen ........................................................................................................................................................................................... 17
Master User Tools Screen ....................................................................................................................................................................... 17
Programming ........................................................................................................................................................................................................ 18
Enter Installer Programming Mode ..................................................................................................................................................... 18
Loading Factory Defaults ................................................................................................................................................................................ 19
Select a Default Configuration.............................................................................................................................................................. 19
Exit Programming Mode .................................................................................................................................................................................. 19
Zone Response Type Definitions
Definiti ons ............................................................................................................................................................. 20
General Information .......................................................................................................................................................................................... 20
System Operation ............................................................................................................................................................................................ 22
Key/Touchscreen Operation ........................................................................................................................................................................ 22
Panic Key/Icons .................................................................................................................................................................................................. 22
Security Codes .................................................................................................................................................................................................... 22
Installer Code .............................................................................................................................................................................................. 22
Master Code ................................................................................................................................................................................................. 22
Enter/Change the Master Code by Installer .................................................................................................................................. 22
Secondary User Codes ............................................................................................................................................................................ 22
Reset Master Code .................................................................................................................................................................................... 23
Security Code Notes ................................................................................................................................................................................ 23
System Displays ................................................................................................................................................................................................. 24
Zone Status Displays ........................................................................................................................................................................................ 24
Audio Alarm Verification (Two-Way Voice Feature) ......................................................................................................................... 25
Activation...................................................................................................................................................................................................... 25
Operator Commands ............................................................................................................................................................................... 25
Event Log .............................................................................................................................................................................................................. 26
Contact ID Event Log Codes ................................................................................................................................................................ 26
Central Station Messages ............................................................................................................................................................................... 27
Testing the System ......................................................................................................................................................................................... 28
-3-

Lyric Controller Installation and Reference Guide

Table of Contents (Continued)
Test Modes ........................................................................................................................................................................................................... 28
Testing the System ........................................................................................................................................................................................... 28
Armed System Test .......................................................................................................................................................................................... 28
Zone Discovery Mode ...................................................................................................................................................................................... 29
Rebooting the System..................................................................................................................................................................................... 29
Lynx Programming Default Values.........................................................................................................................................................
30
Values
Zone Assignment/Alarm Response Type for Configuration 1 ....................................................................................................... 32
Zone Assignment/Alarm Response Type for Configuration 2 ...................................................................................................... 33
Zone Assignment/Alarm Response Type for Configuration 3 and 4 ......................................................................................... 34
Zone Response Type Matrix ...................................................................................................................................................................... 35
Regulatory Agency Statements ............................................................................................................................................................... 36
Limitations of this System Statement .................................................................................................................................................. 37
Agency
Agenc y Notices ................................................................................................................................................................................................ 38
SIA Quick Reference Guide ........................................................................................................................................................................ 39
Specifications .................................................................................................................................................................................................... 39
Glossary ................................................................................................................................................................................................................ 40
Contacting Technical Support ................................................................................................................................................................... 41
Index ....................................................................................................................................................................................................................... 42
Summary of Connections Diagram ........................................................................................................................................................ 43
Warranty Information ................................................................................................................................................................ Rear Cover

-4-

Lyric Controller Installation and Reference Guide

System Features
The Lyric Controller is a self-contained, rechargeable wireless control/communicator that features easy
installation and usage. A built-in speaker provides voice annunciation of system status along with voice
descriptors of each zone. An internal module allows the controller to communicate with the Central Station via
the Internet or (if installed) Cellular Wireless.

ETL

Lyric Controller is not intended for UL985 Household Fire applications u
unless
nless a 2424- hour backup
battery ( p/n 300300 - 03866)
03866) is installed.

System Features












7.0-inch color graphic touch screen
Message center (for user recorded messages)
Voice announcement of system and zone status
Ten user-selectable voice chimes sounds
Reminders
Automatic stay arming
Night stay arming
48 User Codes (Installer, Master, Guest, Duress)
Panic Functions (Police, Fire, Medical)
Programmable Reminders
Video Camera Control (requires WiFi connection)
Supports Mobile Devices (Tablet, iPAD, etc.) that duplicate functions of the Lyric Controller (i.e.;
Security, Web Content Home Automation and Video Control)
Built-in Camera

Home Automation




Integrated Z-Wave Support
Control up to 232 Z-Wave Home Automation devices including:
- Thermostats (up to 6)
- Door locks (up to 6)
- Devices (outlets, switches, lamps/appliances)
Supports Z-Wave Network Wide Inclusion (NWI) Mode
100 programmable Smart Actions
Up to 150 scheduled events
Supports Garage Door Feature (5877 Relay Receiver)

Zones and Devices







Two Hardwire Zone (EOLR, N/C, N/O)
128 Wireless Zones (5800 and SiX™ Series transmitters)
Four Garage Door Zones
32 Wireless Button (Keyfob) Zones (5800 and SiX™ Series transmitters)
Eight (SiX™ Series) Wireless Keypad Zones
12 Temperature Zones
Resident Monitor Zone Types
Built-in Case Tamper

Communication





ADEMCO Contact ID
Integrated WiFi support
Internet Central Station communication
Cellular (GSM or CDMA) Central Station communication
WiFi Central Station communication
Two-way Voice communication

Supports AlarmNet 360

TM

Remote Services

-5-

Lyric Controller Installation and Reference Guide

System Features (Continued)
System Power

Primary Power: Plug-in Power Supply, 110VAC to 9VDC, 2.7A output p/n 300-07332US (TBD in Canada)
Backup battery: Rechargeable nickel-metal hydride battery pack rated at 7.2Vdc. (p/n 300-03864-3PIN
or 300-03866

Alarm Output




Built-in sounder
Steady output for burglary/panic
Temporal (3) pulse output for fire alarms
Temporal (4) pulse output for carbon monoxide alarms
Audio Alarm Verification (AAV)

Programming


Options stored in EEROM
TM
Can be uploaded, downloaded or controlled via AlarmNet 360
using capable Cellular or WiFi
Communications Module
Flash downloading

Other Features



Exit Error feature (detects difference between an actual alarm and exit alarm caused by leaving a door
open after the exit delay expires)
Event log storage (total 6,000 events)
RF jam detection
Advanced Protection Logic™ (APL) (Minimizes the likelihood of the system being disabled before
notification can be sent to the Central Station indicating that the premises have been compromised.)
Lyric™ Lock (Customer Retention Logic) Dealer selectable Lockout (anti-takeover) feature
Displays web content including Local News, Weather and Traffic (requires Total Connect Service)
Dealer/Central Station messages (requires Total Connect Service)

Built-in IR camera




-6-

Lyric Controller Installation and Reference Guide

Installing
Installing the Control
Battery Installation
The Lyric Controller is equipped with an integral, replaceable, rechargeable battery pack rated at 7.2Vdc. In the
event of an AC power loss, the system is supported by the long life backup battery that is supervised for
connection and for low voltage conditions. If the battery is missing, or a low battery condition is detected, a
“low battery” message is displayed and a report is sent to the Central Station. In addition, the system will beep
once every 45 seconds to audibly indicate a low battery condition (press any key to stop the beeping). Select
the appropriate battery pack, based on the installation’s requirement, and install the battery pack. Follow the
steps and refer to the figure below to install and connect the battery.

Battery Selection
Select the appropriate battery pack, based on the installation’s requirement, and install the battery pack.
Battery Part Number
300-03864-3PIN
300-03866

Battery StandbyTime
4-hours (minimum)
24-hours (minimum)

Low Battery Notification
Approximately 1-hour before battery depletion
At least 1-hour before battery depletion

Installing the Rechargeable Backup Battery
1.
2.
3.
4.
5.
6.
7.

Insert the battery pack into controller’s rear case.
Install the battery retainer.
Secure the battery retainer with the provided screws (2).
Connect the battery pack connector to the receptacle on the back of the controller.
Align the slots on the back of the controller with the hooks on the wall mount as shown below.
Once attached, insert the screw to secure the controller to the wall mount.
Plug the power supply into a 24-hour, 110VAC unswitched outlet. Upon power-up, the system will display
the “System Standby!” screen will be displayed.

RETAINER

RETAINER

STANDARD CAPACITY
BATTERY PACK
(p/n 300-0364-3PIN)
SCREWS (2)

HIGH CAPACITY
BATTERY PACK
(p/n 300-03866)

SCREWS (2)

OR

lyric-031-V0

Rechargeable batteries may take up to 4848- hours to fully charge. The “Low Battery” message
should clear within four hours or by entering Test Mode.

Replacing the Rechargeable Backup Battery
1.
2.

When battery replacement is required, at the Master User screen select the “Advanced” icon.
Select “Install Backup Battery” and follow the displayed steps to replace the battery or follow the steps
below.
Remove the battery
1. Unscrew the screw securing the controller to the wall mount (if used).
2. Release the catch that secures the controller to the wall mount.
3. Rotate the controller away from the wall and lift it from the wall mount, being careful not to damage the
wiring.
-7-

Lyric Controller Installation and Reference Guide

Installing the Control (Continued)
4.
5.
6.
7.

Disconnect the battery pack connector from the receptacle on the back of the controller.
Remove the screws (2) that secure the battery retainer and remove the battery retainer.
Remove the battery pack from the back case.
Install a replacement battery pack (p/n 300-03864-3PIN OR p/n 300-03866) into the back of the
controller.
8. Install the battery retainer.
Install the replacement battery
1. Secure the battery retainer with the provided screws (2).
2. Connect the battery pack connector to the receptacle on the back of the controller.
3. Align the slots on the back of the controller with the hooks on the wall mount as shown below.
4. Once attached, insert the screw to secure the Lyric to the wall mount.
NOTE: If a Cellular Communication Module is being installed, verify the module’s signal strength before
selecting a final mounting location. Refer to Checking the Signal Strength in the Communications
Module section.

Wall Mounting
For wall mounting follow the steps and refer to the figure below.
1. Feed the field wiring through the appropriate openings in the wall mount.
2. Attach the wall mount to a sturdy wall using the four provided screws.
3. If required, install an additional mounting screw in the case tamper.
4. Align the slots on the back of the controller with the hooks on the wall mount as shown below.
5. Once attached, insert the screw to secure the Lyric to the wall mount.

WALL
MOUNT

MOUNTING
SCREW (4)
TYP.
TAMPER
SCREW
(OPTIONAL)

WALL
SURFACE

INSERT SCREW
(IF APPLICABLE)

lyric-036-V1

-8-

Lyric Controller Installation and Reference Guide

Installing the Control (Continued)
Desktop Mounting
For desktop mounting the Lyric Desk Stand (LCP500-DK) is installed in place of the wall mount. The desk Stand
can be installed in two positions that provide a viewing angle of 30 degrees or 60 degrees. Follow the steps and
refer to the figures below.

Replace the Back Plate
1.
2.
3.

Remove the screw securing the rear cover to the controller.
Remove the rear cover.
Feed the field wiring through the appropriate openings in the rear cover included with the Lyric Desk Stand
(LCP500-DK).
4. Install the new rear cover.
5. Install the screw to secure the rear cover to the Lyric Controller.

INSTALL
SCREW
REMOVE

lyric-050-V0

Install Desk Stand
1. Align the slots on the back of the controller with the hooks on the desk stand as shown below.
2. Insert the stand into the slots on the rear case to provide the desired viewing angle and slide up to lock in
place.
STAND LOCATION 30

STAND LOCATION 60

lyric-052-V0

-9-

Lyric Controller Installation and Reference Guide

Installing the Control (Continued)
AC Power
The Lyric Controller is powered by a 9 Volt DC, 2.7 Amp Plug-in Power Supply, 300-07332US (TBD in Canada).
Refer to the wiring table below for wire gauge and length.
Use only the 300300 - 07332US (TBD Canada) Power Supply. Do not plug the power supply into the AC
outlet until after all wiring connections have been made.

Wiring Overview
The following summarizes the electrical connections associated with the Lyric Controller. Follow the steps and
refer to the figure below when making connections. Refer to the Summary of Connections diagram for
additional information.

Make Electrical Connections
Temporarily hang the controller from the hook on the wall mount.
If used, connect the hardwire sensors/contacts to the HWZ1/HWZ2 (+) and GND (-) terminals.
Connect the Power Supply (p/n 300-07332US) to the +9VDC and GND terminals on the controller.
Align the slots on the back of the controller with the hooks on the wall mount as shown below.
Once attached, insert the screw to secure the controller to the wall mount.
Plug the power supply into a 24-hour, 110VAC unswitched outlet. Upon power-up, the system will display
the “System Standby!” screen will be displayed.

USB PORT

GND

+9VDC

GND

HWZ1

TERMINAL
BOARD
HWZ2

1.
2.
3.
4.
5.
6.

TAMPER

BATTERY
RECEPTACLE

DETAIL A

lyric-035-V1

- 10 -

Lyric Controller Installation and Reference Guide

Installing the Control (Continued)
Communication Modules
The Lyric Controller supports Central Station reporting using wireless/cellular and WiFi communications
devices. They also support upload/download programming capability via the Internet or a Private local area
network (Intranet). This allows site maintenance independent of Central Station monitoring, and modification to
sites globally via the Internet or through a private LAN. Refer to the Programming Guide (p/n 800-16077) for
information regarding programming and registration. Additionally, an internal Z-Wave module allows the Lyric
Controller to support Home Automation functions. (refer to the Lyric User Guide (p/n 800-16078 for additional
information.) The controllers are compatible with the following AlarmNet Communication Modules:
Model
LYRIC-3G
LYRIC-CDMA

Description
GSM Cellular Communications Module
CDMA Cellular Communications Module

Communications
Communications Module 2424- Hour Standby Power
If 24-hour standby is required, the Super High Capacity battery (p/n 300-03866) must be installed.

RF Exposure
E xposure

!

WARNING: The Lyric Controller must be installed to provide a separation distance of at least 7.8
in (20 cm) from all persons and not coco- located or operated in conjunction with any other
transmitter except in accordance with FCC multimulti - transmitter product
product procedures.

Install
Insta ll and Configure
Configur e C ommunication Module
Follow the steps and refer to the figure below to install the Communications Module.

Installing the Cellular Communications Module
1.

Enter Installer Programming then select “Test”
or Enter Master User Programming, then select “Advanced”.
2. Select “Install Cellular Module” and follow the prompts displayed on the controller or follow the steps below.
3. Remove controller side cover (bezel).
4. Remove the screw securing the module to the controller (if installed,).
5. Remove the existing Cellular Communications Module (if installed).
6. Install the Cellular Communications Module into the controller.
7. Ensure that the Communications Module is properly seated into the controller and secure the module with
the provided screw (if required).
8. Insert the side cover (bezel) into the controller.
9. Slide the bezel down to lock it in place and secure the Communications Module.
10. Select OK to complete the installation.
11. Enable the Communications Module, configure alarm reporting and module supervision and register the
device. Refer to the “Program Communicator” and “Communications Diagnostics” sections in the
TM
Programming Guide (p/n 800-16077). OR Log on to the AlarmNet 360 website
(https://webdev2.alarmnet.com/AlarmNetDirect/Account/LogOn).
TM

The Communications Module must be registered with AlarmNet 360 TM before downloading or
alarm reporting can take place.

INSERT
PUSH
DOWN
COMMUNICATION
MODULE

SCREW

DETAIL A
lyric-034-V0

- 11 -

Lyric Controller Installation and Reference Guide

Installing the Control (Continued)
Communication Modules
Checking Signal Strength
When choosing a suitable mounting location, check the communications module’s signal strength to
ensure proper operation. For most installations, using the module’s internal antenna, mounting the
Lyric controller as high as practical, and avoiding large metal components provides adequate signal
strength for proper operation. To check signal strength, perform the following test.
Check Signal Strength
1.

With the System in the Installer Programming mode,
select the “Comm. Diagnostics” button and then select
the “Cellular Information” button. The Cellular
Information will be displayed. The signal strength is
displayed (in dBm) as RSCP if the Lyric-3G module is
operating on the 3G Network or RSSI if the module
Lyric-3G module is operating on the 2G Network and for
the Lyric-CDMA module.

2. Compare the displayed RSCP or RSSI number to the
correct Signal Strength Guide at right to ensure
adequate signal strength. If necessary, relocate the
Controller to obtain better signal strength (select
“Cellular Information” again to refresh the reading).
3. If adequate signal strength cannot be achieved, External
Antenna Kit model Cell-ANTST should be used.

Lyric - 3G Signal Strength
Strength
RSCP (3G)
Good............................................ -20 to -90 dBm
OK ................................................ -91 to -100 dBm
Marginal .................................... -101 to -106 dBm
Bad ............................................. -107 to -120 dBm
RSSI (2G)
Good............................................. -20 to -89 dBm
OK ................................................. -90 to -98 dBm
Marginal ................................... -99 to -104 dBm
Bad ............................................ -105 to -120 dBm
Lyric - CDMA Signal Strength
RSSI
Good............................................. -20 to -90 dBm
OK .................................................-91 to -100 dBm
Marginal .................................... -101 to -106 dBm
Bad .......................................... -107 to -120 dBm

- 12 -

Lyric Controller Installation and Reference Guide

Wireless Zones
General Information
Zones
The Lyric Smart Control supports up to 128 total wireless zones using 5800 and SiX™ Series transmitters, and
wireless keyfobs.

Range
The built-in RF receiver can detect signals from wireless transmitters within a nominal range of 200 feet.

Transmitters
5800 and SiX™ Series transmitters have built-in serial numbers that must be entered into the system using the
TM
“Zones” programming section, or input to the controller via AlarmNet 360 . 5800 Series transmitters (except
the 5800WAVE and 5800RL) do not have DIP switches. Each transmitter's zone number is also programmed
into the system in the “Zones” programming section. Some transmitters, such as the 5816 can support more
than one "zone" (referred to as loops or inputs). On the 5816, for example, the wire connection terminal block is
loop 1; the reed contact is loop 2. Each loop must be assigned a different zone number.
For button transmitters (RF "keyfobs") such as the 5804E and 5834-2/5834-4, you must assign a unique zone
number to each individual button used on the transmitter. Each button on the transmitter also has a predesignated loop or input number, which is automatically displayed.

ETL

The 5816 Transmitters do not
not have EOL supervision
sup ervision of their loop wiring,
wiring , which must not exceed 3
feet.
The 5800PIR5800PIR- OD, 5800RL, 5800SS1, 5804E, 5814, 5816TEMP,
5816TEMP, 5821, 5877 and 5878 wireless
transmitters have not been evaluated by ETL.
ETL.

House Identification
If a 5800WAVE or a 5800RL is being installed with the system, to establish proper communication a RF House
Code (House ID Code) (01–31) must be programmed in the Lyric, and the device must be set to the same code.
Refer to the “System Type” programming section in the Lyric Controller Programming Guide (p/n 800-16077).
An RF House ID is not necessary for other 5800 Series transmitters; the entry should be left at “0” (default) in
those cases.

Transmitter
Transmitter Supervision
With the exception of some transmitters/keypads that may be carried off-premises (5804E, 5834-2/5834-4
and SiXFOB), each transmitter is supervised by a check-in signal that is sent to the receiver at 70–90 minute
intervals. If at least one check-in is not received from each supervised transmitter within a 12-hour period, the
"missing" transmitter zone number(s) and "Supervision" will be displayed. The supervision for a particular
transmitter in the system that may also be carried off the premises may be turned off by entering it as an
“Unsupervised” type. For additional information, refer to the “Zones” programming section in the Lyric
Controller Programming Guide (p/n 800-16077). 5800 and SiX™ Series transmitters have built-in tamper
protection and will annunciate as a fault condition if covers are removed. In Canada the RF supervision period
is 3-hours for Fire zones and 12 hours for all other zone types.

Transmitter Input Types
Each transmitter has one or more unique factory-assigned input (loop/5800 Series or service/SiX™ Series) ID
codes. Each of the inputs requires a programming zone (e.g., a 5804E's four inputs require four button zones).
Transmitters can be entered as one of the following types (see transmitter’s instructions for appropriate
Supervision type):
Type
Supervised
Unsupervised
Button

Description
Sends periodic check-in signals, as well as fault, restore, and low battery signals. The
transmitter must remain within the receiver's range.
Sends all the signals that the Supervised type does, but the controller does not supervise the
check-in signals. The transmitter may therefore be carried off-premises.
Sends only fault signals. Do not send low battery signals until being activated. The
transmitter is unsupervised and may be carried off-premises.

Transmitter Battery Life

Batteries in the wireless transmitters may last from 4–7 years, depending on the environment, usage, and
the specific wireless device being used. Factors such as humidity, high or low temperatures, as well as large
swings in temperature may all reduce the actual battery life in a given installation. The wireless system can
identify a true low battery situation, thus allowing the dealer or user of the system time to arrange a change
of battery and maintain protection for that point within the system.
Button-type transmitters should be periodically tested for battery life. The 5804E, 5834-2/5834-4, 5878 and
SiXFOB button transmitters have replaceable batteries.
- 13 -

Lyric Controller Installation and Reference Guide

Wireless Zones (Continued)
5800 Series Transmitter Loop Numbers
(Refer to this information when programming 5800 Series transmitters)
The following illustration shows the compatible transmitters, their associated input types and loop designations.

LOOP
1
LOOP 1
LOOP
1

LOOP 1
(LOW
SENSITIVITY

LOOP 1
(LOW
SENSITIVITY

LOOP 2
(HIGH
SENSITIVITY)

LOOP 2
(HIGH
SENSITIVITY)

LOOP 3 (TEMP)

LOOP 3 (TEMP)
LOOP 4 (TAMPER)

LOOP 4 (TAMPER)
5800Micra
ENROLL AS
SUPERVISED

5800CO
ENROLL AS
SUPERVISED

5800PIR-RES
ENROLL AS
SUPERVISED

5800PIR-OD
ENROLL AS
SUPERVISED

5800PIR/5800PIR-COM
ENROLL AS
SUPERVISED

5800RL
SET HOUSE ID

LOOP 3
LOOP 4
LOOP
1

LOOP 1

LOOP 2
LOOP 1

OF

F

LOOP 1

LOOP 1

5804E
ENROLL AS BUTTON

LOOP 2
(REED)

LOOP 2
(REED)

LOOP 3
(TERMINALS)

LOOP 1

ALTERNATE
POSITION
FOR LOOP 2
5816MN
ENROLL AS
SUPERVISED

LOOP 1
(TERMINALS)
5819
ENROLL AS
SUPERVISED

5818MNL
ENROLL AS
SUPERVISED

SERIAL #2
LOOP 1

SERIAL #1
LOOP 4

5834-2
ENROLL AS BUTTON

SERIAL #1
LOOP 3
SERIAL #1
LOOP 2

1
2
3
4

5819S (WHS & BRS)
ENROLL AS
SUPERVISED

5820L
ENROLL AS
SUPERVISED

5821
ENROLL AS
SUPERVISED

SERIAL #1
LOOP 1

LOOP 1
(HIGH
SECURITY)
LOOP 2
(STANDARD
SECURITY)

SERIAL #1
LOOP 1

SERIAL #2
LOOP 2

SERIAL #2
LOOP 3

LOOP 1
(INTERNAL
SHOCK
SENSOR

SERIAL #2
LOOP 4

LOOP 3

ST
AY

LOOPS
1-3

LOOP 1
SERIAL #2
LOOP 3

AW
AY

LOOP 1

SERIAL #2
LOOP 1
SERIAL #1
LOOP 2

SERIAL #1
LOOP 4

5814
ENROLL AS
SUPERVISED

LOOP 3 (TILT MODE)
LOOP 4 (TAMPER)
5853
ENROLL AS
SUPERVISED

5834-4
ENROLL AS BUTTON

5869
ENROLL AS
SUPERVISED

5870API
ENROLL AS
SUPERVISED

LOOP 1
(LOW SENSITIVITY)
LOOP 2
(HIGH SENSITIVITY)

lyric-053-V1

SERIAL #1
LOOP 3

LOOP 2
(REED)

5811
ENROLL AS
SUPERVISED

LOOP 3
(TERMINALS)

LOOP 1
(TERMINALS)

5816
ENROLL AS
SUPERVISED

5809
ENROLL AS
SUPERVISED

5806/5806W3/5807
5808/5808LST/5808W3
ENROLL AS
SUPERVISED

LOOP 2
(REED)

LOOP 1
(TERMINALS)

5822T
ENROLL AS
SUPERVISED

LOOP 1

LOOP
1

5 8 0 0 WAV E
P RO G R A M
HOUSE ID

5800SS1
ENROLL AS
SUPERVISED

ON

SERIAL #2
LOOP 2
5877

5878
ENROLL AS BUTTON

5898
ENROLL AS
SUPERVISED

Notes: (1) The 5806W3 smoke detector must be used in SIA applications.
(2) Button type devices send only fault and low battery signals; no restore or check-in signals.
Supervised RF devices send periodic check-in signals, faults, restore and low battery signals.
(3) If an external sounder is required, the 5800WAVE should be used.
(4) The 5804E and 5834-4 encrypted (High-Security) devices must be activated while the system is in
Go/No-Go Test Mode. Refer to the transmitter’s Installation Instructions for complete details. The
system will confirm the enrollment of the encrypted device by beeping two times.
(5) The 5800PIR-OD, 5800RL, 5800SS1, 5804E, 5814, 5816TEMP, 5821, 5877, and 5878 wireless
transmitters have not been evaluated by ETL.

- 14 -

Lyric Controller Installation and Reference Guide

Mechanics of Programming
Navigating Menus
TouchTouch -screen Display
The LYRIC Controller’s Liquid Crystal Display (LCD) touch-screen displays variable icons and text on “screens”.
The screen displays status icons and associated text, the current time and date, system status information and
menu choices. The Menu area includes a list of commands, or choices that apply to the current selection. The
status area provides information about various system events and a colored bar also provides an indication of
system status. A “Home Screen” is displayed whenever power is applied to the system. In addition, the Home
Function key is lit Green when the system is ready or flashes when it is not. When the system is armed the Home
Function key is lit Red.

Ready To Arm - Chime

12:00PM
December 31, 2014

Security

Automation

Video

Smart Scenes

Notices

Settings

66F
Mostly Sunny

5-Day Forecast

lyric-009-V1

TM

LYRICTM Controller
Key

Description
Panic key - Initiates panic alarm options when selected for 4
seconds.
Home key - Used to exit from a screen or return to the home screen

- 15 -

Lyric Controller Installation and Reference Guide

Mechanics of Programming (Continued)
Navigation Keys
Navigating through the screens is accomplished by lightly touching the icons or menu items on the touchscreen. Once activated, the controller advances to the next screen. Selecting the “Home” (cancel) key or the “”
key will return you to the previous screen at any time unless System Programming mode is active. By touching
(selecting) an icon or key the system, depending on the function, advances to another screen, toggles between
options or scrolls through multiple options that can be selected. The system provides a prompt when a specific
input is required.
Note: You may find it convenient to adjust the volume setting before entering the Program Mode. This will
allow you to clearly hear the feedback announcements or system beeps from the system’s built-in
speaker. To adjust the volume, select “Settings” on the Home screen. Adjust the volume using the slide
displayed on the Settings screen and then select “Save” to accept. Upon exiting the Program Mode, the
system resets the volume to the default value (mid-level).

Home Screen
System Status is displayed at the top of screen. In addition to the system status, the Home Screen displays the
current date and time and Security, Automation, Video, Smart Scenes, Notices Settings and Help Videos icons
on two pages. When Total Connect Services are connected and web content is enabled, News and Traffic icons
are displayed along with the current weather forecast and a 5-Day Forecast button. Selectable options are
displayed on two pages. Select the “>” and “Lyric Controller Installation and Reference Guide

Mechanics of Programming (Continued)
Navigating Menus
Security Screen
Ready To Arm - Chime

System Status is displayed at the top of each screen and
the time and date are displayed at the bottom of the
Security Screen. The Security Screen displays the system
status and selection “icons” and “tabs”. The displayed
pages and options may vary slightly depending upon the
devices and services that are installed in or connected to
the system.

SYSTEM

TOOLS

MESSAGE

ZONES

Ready To Arm

ARM AWAY

ARM STAY

Delay

ARM CUSTOM

9:11 AM December 17, 2014
lyric-019-V1

Security Screen (Page 1)
Selection
Arm Away
Arm Stay
Arm Custom
System
Tools
Message
Zones
Delay/Instant

Function
Used to Arm the system in Away mode (displayed on both Home Screen pages).
Used to Arm the system in Stay mode (displayed on both Home Screen pages).
Used to Arm the system in Custom mode (displayed on both Home Screen pages).
Provides information about system status.
Provides access to Installer and User Programming Menus (Master User Code required for
access).
Provides access to Message Center (displayed on both Home Screen pages).
Provides access to Zone information and options.
Used to toggle between exit delay and instant arming options (displayed on both Security
Screen pages).

Master User Tools Screen

Ready To Arm - Chime

The Master User screen provides access to the User
configurable features and displays options on two
pages. Entering the Master User Code is required to
access the User Tools Menu. Select the “›” to advance
to the second page.

Users

Events

Advanced

Keypad

Date Time

Reminders

Voice Command

WiFi Config

Back
lyric-018-V2

Master User Tools Menu Screen (Page 1)

- 17 -

Lyric Controller Installation and Reference Guide

Mechanics of Programming (Continued)
(Continued)
Programming
If the system is Armed or in Alarm, the Tools icon will not be functional. The system must first
be disarmed.

E nter Installer Programming Mode
SCREEN

ACTION
1.

System Standby!

2.
3.
4.

12:00PM
December 31, 2014

Security

Automation

Video

5.
Smart Scenes

Notices

Settings

lyric-037-V0

6.

System Standby Screen

System Programming...
Installer Code

System Type

Date Time

Communicator

Zones

Comm Diagnostics

Keys

Reporter

Sounder

System Settings

Power-up the controller and allow it to “boot-up”.
“System Standby” is displayed on the touch screen.
When the “boot-up” is complete (approximately 1-2
minutes) “Ready to Arm” is displayed.
Select the “Security” icon.
Select “Tools” icon.
Enter the Installer Code 4112 on the displayed
keypad.
The Installer Tools menu screen appears. Select the
“Program” button. “System Programming…” is
displayed and the “Panic” button is lit and the
“Home” button alternately flashes red and green.
Select one of the following options:
Installer Code
System Type
Date Time
Communicator
Zones
Comm. Diagnostics
Keys
Reporter
Sounder
System Settings
Use the down “˅” arrow to scroll to the next page
of options.
Default Config.
Z-Wave
Reset Master Code
Language*
RF Keypad

7.

The system advances to the Programming screen
for the selected option.
* This programming field may not be available with the
system being installed.

lyric-026-V0

Installer Tools Menu Screen

- 18 -

Lyric Controller Installation and Reference Guide

Mechanics of Programming (Continued)
Loading Factory Defaults
To load the factory defaults, enter the Installer Programming Mode and advance to second page of the System
Programming and refer to following procedure. Refer to the Programming Default Values section of this manual
to view the Default Values.
If a default configuration is loaded, any data that has already been programmed into the system
will be changed according to the default configuration selected!

Select a Default Configuration
SCREEN

ACTION
1. Select “Default Configuration” to display the following
options:

System Programming...
Default Config

Z-Wave

Reset Master Code

Language

Default Config 1
Default Config 3

RF Keypad

lyric-039-V1

Default Config 2
Default Config 4

Note: For a list of the pre-programmed defaults refer to
the Programming Default Values section.
2. Select the desired Default Configuration.
3. A Confirmation screen is displayed.
4. If “Yes” is selected, the System beeps three times and
returns to the Default option screen.
5. If “No” is selected, the System returns to the Default
option screen.

Exit Programming
Program ming Mode
1.
2.
3.

Select the “” key to exit the current screen.
Select the “” key again to return to the Security Screen
Select the “” key again OR select the Home button to return to the Home Screen.

- 19 -

Lyric Controller Installation and Reference Guide

Zone Response Type Definitions
General Information
During programming, you must assign a zone type to each zone, which defines the way in which the system
responds to faults in that zone. Zone types are defined below.
Type
Not Used
Entry/Exit 1
(Burglary)

Function

Characteristics

Used to program a zone that is not used.
Usually assigned to sensors or contacts on
primary entry and exit doors.





Entry/Exit 2
(Burglary)

Usually assigned to sensors or contacts on
secondary entry and exit doors that might be
further from the keypad (typically used for a
garage, loading dock, or basement door).

Perimeter
(Burglary)
Interior, Follower

Usually assigned to all sensors or contacts on
exterior doors and windows
Usually assigned to a zone covering an entry
area (i.e.: foyer, lobby, or hallway) that one must
pass upon entry (after faulting the entry/exit
zone) to reach the keypad. It provides an instant
alarm if the entry/exit zone is not violated first,
and protects an area in the event an intruder
has hidden on the premises before the system is
armed, or gains access to the premises through
an unprotected area.
Usually assigned to a zone that covers a
sensitive area (i.e.: stock room, drug supply
room, etc.) It can also be used on a sensor or
contact in an area where immediate notification
of an entry is desired.
Usually assigned to a zone containing an
Emergency button (silent emergency).

Trouble by Day/
Alarm by Night

24-hour Silent
Alarm













24-hour Audible
Alarm

Usually assigned to a zone containing an
Emergency button (audible emergency).


24-hour
Auxiliary Alarm

Usually assigned to a zone containing a
button for use in personal emergencies or to
a zone containing monitoring devices (i.e.:
water or temperature sensors, etc.).
Usually assigned to a zone containing an
Emergency button (audible emergency).

Local Alarm

Interior with Delay

Provides entry delay (using the programmed
entry time), if tripped when the controller is
armed in the Away mode. Bypassed when the
controller is armed in the STAY or STAY
INSTANT mode.

Fire No
Verification

Can be assigned to any wireless zone used as a
fire zone. This zone type is always active and
cannot be bypassed.

Fire with
Verification

Can be assigned to any wireless zone used as a
fire zone. Fire with verification is available with
smoke detector device type. It cannot be used
with heat detectors, combination heat/smoke
detectors, wireless sensors or fire pull stations.
This zone type is always active and cannot be
bypassed.









- 20 -

None
Entry delay #1 is programmable.
Exit delay is independently programmable.
Exit and entry delays when armed in AWAY, STAY or NIGHT
STAY mode.
No entry delay when armed in STAY INSTANT or AWAY
INSTANT mode.
Exit delay regardless of the arming mode selected.
Entry delay #2 is programmable.
Exit delay is independently programmable.
Secondary entry delay, if armed in the AWAY or STAY mode.
No entry delay when armed in the STAY INSTANT or AWAY
INSTANT mode.
Exit delay begins regardless of the arming mode selected.
Instant alarm, when armed in AWAY, STAY, STAY NO DELAY,
NIGHT STAY or AWAY INSTANT mode.
Delayed alarm (using the programmed entry/exit time) if
entry/exit or interior-with-delay zone is faulted first.
Instant alarm in all other situations.
Active when armed in AWAY or AWAY INSTANT mode.
Bypassed automatically when armed in STAY, NIGHT STAY or
STAY INSTANT mode.

Instant alarm, when armed in AWAY, STAY, NIGHT STAY , STAY
INSTANT, or AWAY INSTANT (night) mode.
Provides a latched trouble sounding from the keypad and, if
desired, a Central Station report when disarmed (day).
Sends a report to the Central Station but provides no keypad
display or sounding.
In disarmed state sends a report to the Central Station displays
"Not Ready to Arm" on the keypad and “AWAY”, “STAY” and
“TOOLS” buttons are disabled.
Follows sounder timeout
Sends a report to the Central Station, and provides alarm sounds
at the keypad.
Sends a report to the Central Station and provides an alarm
sound at the keypad. (There is no keypad timeout.)

Follows sounder timeout
Provides alarm sounds at the keypad.
No reports to the Central Station.
Entry delay #1 (with programmed entry time) when armed in the
AWAY mode.
Entry delay begins whenever sensors in this zone are violated,
regardless of whether an entry/exit delay zone was tripped first.
No entry delay when armed in the AWAY INSTANT mode.
Exit delay regardless of the arming mode selected.
Alarm sound will pulse (Temporal Fire) when this zone type is
alarmed.
Alarm sound will pulse (Temporal Fire) when this zone type is
alarmed and the the alarm has been verified.
System verifies alarm by delaying reporting and alarm sounding
for 30 seconds after alarm is detected. If the zone remains faulted
after 30 seconds a fire alarm is provided. If any other fire zone is
faulted during the 30 second delay window a fire alarm is
immediately provided for that zone. An alarm for original fire
zone will also be provided, if that zone is still faulted. If there are
no fire alarms after the 30 second delay expires, the system will
open a 60 second window. If any fire zone is faulted during that
window a fire alarm will immediately be provided for that zone.

Lyric Controller Installation and Reference Guide

Zone Response Type Definitions (Continued)
Type
24-hour Carbon
Monoxide Monitor
Arm–Stay

Function

Characteristics
Characteristics

Can be assigned to any wireless zone with a
carbon monoxide detector. This zone type is
always active and cannot be bypassed.
Special-purpose zone type used with 5800 and
SiX™ Series wireless keyfobs.

Local keypad and detector will sound when this zone type is
alarmed. (Pulse Temporal 4)

• Exit delay regardless of the arming mode selected.
• System is armed in the STAY mode when the zone is activated.
• System is armed in the AWAY mode when the zone is activated.

Arm–Away

Special-purpose zone type used with 5800
and SiX™ Series wireless keyfobs.

Disarm

Special-purpose zone type used with 5800
and SiX™ Series wireless keyfobs.

• Disarms the system when the zone is activated.

No Alarm Response

Assigned when no-alarm response is required

Silent Burglary

Usually assigned to sensors or contacts on
exterior doors and windows where sirens are
NOT desired.

• No reports to the Central Station.
• No keypad sounding or chime
• System can still be armed
• No display on the screen
• Instant alarm, with No audible indication when armed in the
AWAY, STAY, STAY NO DELAY, NIGHT STAY, or AWAY INSTANT
mode.
• Report sent to the Central Station.

Monitor

Can be assigned to any wireless zone used for
asset protection. Works as a dynamic monitor
of a zone fault/trouble (not alarm).

General Monitor

Assigned sensors or contacts on doors and
windows or asset protection within the
premises. Used to track activity of the occupant
and alert occupant of the activity of others.

General Response

Assigned sensors or contacts on doors and
windows or asset protection within the
premises. Used to track activity of the occupant
and alert occupant of the activity of others.















Resident Monitor

Resident
Response

Used to monitor a resident in an area deemed to
be dangerous by a caregiver.

Used to monitor a resident in an area deemed to
be dangerous by a caregiver. Requires
acknowledgement by caregiver.










Trouble

Used with Other response type

Garage (Burglary

Assigned to Automatic Garage Door
applications. Provides a status of the garage
door close/open real time state




Garage Monitor

Assigned to Automatic Garage Door
applications. Provides a status of the garage
door close/open real time state






- 21 -

Reports to the Central Station, if enabled.
Fault/restore events are logged by the system.
Activity Zone No. and Zone Descriptor displayed on LCD.
Restore will be stored in event log.
No keypad sounding or chime
System can still be armed
No reports to the Central Station.
Fault/restore events are logged by the system.
Monitors entry into a monitored area. Activates a one-time
announcement when faulted.
Activity Zone No. and Zone Descriptor displayed on LCD.
No reports to the Central Station.
Fault/restore events are logged by the system.
Monitors entry into a monitored area. Activates a zone
announcement when faulted.
Activity Zone No. and Zone Descriptor displayed on LCD.
System re-triggers audible sounding every ten seconds until
acknowledged (Off sequence or wireless keyfob).
No reports to the Central Station.
Monitors entry into a monitored area. Activates a zone
announcement when faulted.
Activity Zone No. and Zone Descriptor displayed on LCD.
Fault/Restore events are not logged by the system.
No reports to the Central Station.
Monitors entry into a monitored area. Activates a zone
announcement when faulted.
Activity Zone No. and Zone Descriptor displayed on LCD.
System re-triggers audible sounding every ten seconds until
acknowledged (Off sequence or wireless keyfob).
Fault/Restore events are not logged by the system
The system will provide a trouble sounding from the keypad (and
a Central Station report, if desired).
Associated With Entry Delay #2 Programmed Time.
Exit delays when armed in AWAY, STAY or NIGHT STAY mode.
No Entry Delay when armed in Away or Stay Instant modes.
System can be armed with zone in the faulted state. When the
zone is closed it will automatically be inclusive within protection
points. If the point is subsequently violated, it will initiate an alarm.
Can be assigned to any wireless zone used for automatic “Garage
Door” Open/Close status.
Will not initiate an alarm condition on the controller.
When zone is in the open state will display “FAULT.”
Does not report alarms to Central Station.
Zone will chime if enabled to do so
System can be armed if this zone type is in fault

Lyric Controller Installation and Reference Guide

System Operation
Key/Touchscreen
Key/Touchscreen Operation
The touchscreen icons allows the user to arm and disarm the system, and perform other system functions, such
as bypassing zones. Zone and system conditions (alarm, trouble, bypass) are displayed on the LCD. When an
alarm occurs, the console and external sounder (if installed) will sound, and the zone(s) in alarm will be
displayed. Pressing any key will silence the keypad sounder for 10 seconds (only once). Disarming the system
will silence both console and external sounders. When the system is disarmed, any zones that were in an alarm
condition during the armed period will be displayed (memory of alarm). To clear this display, simply repeat the
disarm sequence by selecting the Disarm button and entering the Security Code. The console also features
chime annunciation, and three panic key icons for silent, audible, fire or personal emergency alarms. These keys
can notify the Central Station of an alarm condition, if that service is connected.

Panic Key/Icons
Key/Icons
There are three panic icons that are displayed (if programmed) when the “Panic” key is selected for
approximately four seconds. The panic key screen will timeout if a selection is not made within ten seconds.
The keys can be used to manually initiate alarms and send a report to the Central Station. Each can be
individually programmed for 24-hour silent, audible, personal or fire emergency responses. The panic function is
activated when the respective keys is pressed. The panic functions are identified by the system as follows:
Zone
995
996
998
999

Function
Fire Emergency
Medical Emergency
Local Alarm
Police Emergency

Important: For the silent panic functions to be of practical value, the system must be connected to a Central
Station.

Security Codes
Installer Code
The installer programs the 4-digit Installer Code initially as part of the programming procedure. The
factory default Installer Code is 4- 1- 1- 2, but may be changed in the Installer Code programming field.
The Installer Code is the only code that allows entry into Installer Programming mode.

Master Code
In normal operation mode, the Master (Security) Code is used to enter the 4-digit User Security Codes.

E nter/Change
nter/ Change the Master Code by Installer
I nstaller.
nstaller.
The factory default Master Code for the Lyric Controller is set to 1-2-3-4. The Master Code is used to enter the
4-digit User Security Codes.
SCREEN

ACTION
1.

Ready To Arm - Chime

Users

Events

Advanced

Keypad

Date Time

Reminders

Voice Command

WiFi Config

2.
3.

4.
5.

After entering the User Tools/Programming Menu, select the
“Users” icon on the User Menu screen. The system displays the
User Code Programming screen.
Select “Master”, then select “Edit”.
Enter a new 4-digit Master (Security) Code on the displayed
keypad. The system displays the new code on the left side of the
screen.
Select “Done” when you are finished.
The system returns to the Master Code Programming screen.

Back
lyric-018-V1

Secondary
Secondary User Codes
In normal operation mode, the Master (Security) Code can be used to assign up to 46 secondary 4-digit security
codes, including a Guest Code and a Duress Code. The Master Code can also be used to individually remove
secondary codes from the system. Refer to the Lyric Controller User Manual for additional information.

- 22 -

Lyric Controller Installation and Reference Guide

System Operation
Reset Master Code
1.

After Entering the Installer Programming Mode, select “Reset Master Code” from the second page of the
Installer Programming Tools menu.
The system displays a confirmation screen. Select the “Yes” key to reset the Master User Code to “1234”.
If confirmed, the Master Code will be reset back to “1-2-3-4”. This will be logged in the System Event Log as
“Reset Master Code User 2 E655”. The system returns to the second page of the Installer Programming
Tools menu. OR
If the reset failed, the system will display: “Command Failed. Unable to Reset Master Code”.

2.
3.





Security Code Notes
The Master and Secondary security codes permit access to the system for arming, disarming,
etc.
The Installer Code can disarm the system only if it was used to arm it. In addition, the Installer
Code cannot disarm the system if it was armed by pressing and holding a Quick-Arm button.
The Guest Code can disarm the system only if it was used to arm it. In addition, the Guest Code
cannot disarm the system if it was armed by pressing and holding a Quick-Arm button.
Duress code sends a special code to the Central Station when used to perform any system
operation. Instruct users to be careful not to use this code for normal usage.
Opening/closing reports are sent for the Installer Code, with the appropriate subscriber
number. Master Code and secondary user codes are sent as User No. 2 and 3-48 respectively, in
Contact ID® format (with the appropriate user number).

- 23 -

Lyric Controller Installation and Reference Guide

System Operation
System Displays
The following icons will be displayed on the Home screen along with specific zone status information (if
applicable) to indicate system status.
DISPLAY
DEFINITION
DISPLAY
DEFINITION
DISPLAY
DEFINITION
AC Loss
901 Expansion
Temperature
Module Tamper

Alarm

950 Comm.
Trouble

Other

(Intrusion)

Ready To Arm

988 RF Jam

Automation

(5800 Series
Wireless Device)

(Z-Wave Node
Failure)

990 RF Jam

Fault *
Garage Door

Armed Away

(SiX Series
Wireless Device)

Armed Stay

992 Comm.
Trouble

WiFi source
present and
signal strength

Armed Night
Stay

997 Local
Alarm

No WiFi source

Armed Custom

Door Open

Not Ready To
Arm

Window Open

Battery Low

Fire
OR
Heat Sensor
Environmental

Bypassed
Zones
CO Alarm

Flood

Reporter
Failure

Glass Break

Low Batt
850 Keypad

Medical Alarm

900 Cover
Tamper

Motion

Zone Status Displays
The icons associated with the programmed zones are displayed on the Zones screen. The icon’s color
indicates the zone status (i.e.; yellow icon indicates the zone is faulted and a red icon indicate the zone
is in alarm). In addition a bypass icon is displayed alongside the icon for a bypassed zone.

- 24 -

LYNX Touch Installation and Setup Guide

System Operation (Continued)
ETL

Audio alarm verification has not been evaluated by ETL
ET L.

Audio Alarm Verification (Two(Two- Way Voice Feature)
This feature allows the Central Station operator to listen, talk to or conduct a two-way conversation with an
individual(s) at the premises. It also assists the operator in gathering information about the nature and location
of the alarm that may be helpful in responding to police and fire departments. All Lyric Controllers are capable
of supporting the Two-Way Voice feature. The Lyric Controller does not make system announcements when the
Two-Way Voice feature is active.
If a WiFi connection is being used for Two-Way Voice (AAV), sufficient bandwidth must be available.

AAV requires a continuous WiFi upload/download bandwidth of 90kbps for proper operation.

WiFi bandwidth less than 90kbps may result in degraded performance.

Activation
Fire and CO alarms will prevent the Lyric Controller from starting an AAV session. A new Fire or
CO alarm will end an AAV session that is in progress.
The controller sends the “alarm message” followed by a “Listen-in-to-Follow message” (Contact ID® code 606)
to the Central Station. The Listen-in-to-Follow message causes the Central Station’s digital receiver to
temporarily hold the phone line for approximately 1 minute. When the controller receives the “kissoff” from the
Central Station, indicating that the alarm message has been received, the Two-Way Voice (AAV) feature is
activated in the (default) “Listen Mode” and sirens and keypad sounds are discontinued. The controller transmits
a beep acknowledgment to the Central Station, once per second. The beep alternates between two tones and
indicates that the controller is waiting for a session command from the Central Station operator. Once a
command is issued the beep acknowledgement is discontinued, however, if a command is not issued within two
minutes the system will “time out” and the call will be terminated.
Operator Commands
The Central Station operator begins the session, which last 5 minutes, by entering one of the valid AAV
commands shown in the table below. The session may be extended 5 minutes, without changing the operating
mode, by pressing the [7] key on the touch-tone phone. Selecting another operating mode also resets the
session an additional 5 minutes. During the last minute of the 5 minute, session, the controller generates two
beeps every 30 seconds to alert the Central Station operator that the session is about to time out. The Central
Station operator may then extend the session by pressing the [7] key on the touch-tone phone. If the session is
not extended, the phone line is disconnected and the session is ended. Sessions may be ended at any time by
pressing the [9] key on the touch-tone phone. The AAV modes are described as follows:
Note: When entering AAV commands make sure the Central Station receiver has been disconnected
from the phone line, otherwise AAV commands may not go through.
Key
1

Function
Talk Mode: Pressing the [1] key on the touch tone phone, enables one-way voice communication
from the Central Sation to the violated premises, and allows the operator to communicate through
the controller’s built-in speaker. In this mode the controller’s Panic and Home buttons blink
alternately.

2

VOX (Voice) Mode: Pressing the [2] key on the touch-tone phone, enables two-way voice
communications between the Central Station and the violated premises via the controller’s built-in
speaker and microphone. In this mode the controller’s Panic button is lit Red and the Home button is
alternately lit Red and Green.

3

Listen Mode: Pressing the [3] key on the touch-tone phone, Enables one-way audio from the violated
premises to the Central Station. The Listen Mode is the start up default mode of the voice feature and
allows the operator to listen through the controller microphone. This mode does not affect the existing
LED pattern.

7

Extends the session 5 minutes without changing its operating mode.

9

Ends the session and disconnects the phone line.

- 25 -

Lyric Controller Installation and Reference Guide

System Operation
Event Log
The Lyric Controller Series event log is capable of recording and displaying up to 6,000 system events. These
events are stored locally in the controller and transmitted to the Central Station. When the maximum number of
events is reached in the Event Log, the system will overwrite the oldest event first. The type of events that can
be recorded is selectable and is programmed in the System Type programming field. The event log can be
reviewed by entering the Installer Programming or Master User Programming mode and selecting “Events”.
Refer to the Lyric Controller User Manual for additional information. The Events and CID Codes displayed vary
according to the options that are programmed. The table below provides definitions of the events/codes that
may be displayed by the controller.
Note: In the unlikely condition that the backup battery becomes fully discharged when AC power is lost, any system
activity performed after the low battery notification will not be saved in the event log. Additionally, the
controller will revert to the status condition as before the low battery notification.

Contact ID® Event Log Codes
CID Code
110
121
122
123
131
132
134
135
137
145
146
150
162
301
302
305
308
316
339
341
344
350
353
373
374
380
381
383
384
401
403
406
408
441
455
459
570
601
602
606
607
623
627
628
654
655
759
760
761
762
1401

Definition

Event Log Display
Fire
Duress
Silent
Audible
Perimeter
Interior
Entry/Exit
Day Night
Tamper
Expansion Module Tamper
Silent Burglary
24 Hour Non-Burglary
Carbon Monoxide Detected
AC Loss
Low system battery
System Reset
System shutdown
System Tamper

Alarm, Fire
Alarm, Duress
Alarm, Silent
Alarm, Audible
Alarm, Perimeter
Alarm, Interior
Alarm, Entry/Exit
Alarm, Day/Night
Alarm, Tamper
Expansion Module Tamper
Silent Burglary
24-Hour Non-Burglary
Carbon Monoxide Detected
Trouble, AC Loss
Trouble, Low System Battery
Trouble, System Reset
System shutdown
System Tamper*
Expansion Module Power On/Reset
Trouble, Case Tamper
Trouble, RF Receiver Jam Detect
Communication Path Failure
Trouble, Long Range Radio Transmitter Fault
Trouble, Fire Trouble
Trouble, Exit Error Alarm
Trouble, Sensor
Trouble, Loss of Supervision RF
Trouble, Sensor Tamper
RF Low Battery
Open/Close by User
Open/Close Automatic
Cancel
Quick Arm
Armed Stay
Auto-Arm Failed (Logged in Event Log Only)
Recent Close
Zone/Sensor Bypass
Manual Trigger Test Report
Periodic Test Report
Listen-in to follow
Walk Test
Event 90% Full
Program Mode Entry (Logged in Event Log Only)
Program Mode Exit (Logged in Event Log Only)
System Inactivity
Reset Master Code (Logged in Event Log Only)
Resident Monitor Zone Response
Resident Response Zone Response
General Monitor Zone Response
General Response Zone Repsonse
Local Alarm

Cover Tamper
RF Jam Detect
Comm. Trouble
Fire trouble
Exit error alarm
Sensor trouble
Superv Loss-RF
Sensor Tamper
RF Low Battery
Arm Away/Disarmed
Automatic O/C
Cancel
Quick arm
Arm Stay/Disarmed
Auto-arm Failed
Recent Closing
Zone Bypass
Manual trigger test
Periodic test report
Listen-in to follow
Walk Test Mode
Event Log 90% Full
Program mode entry
Program mode exit
System Inactivity
User Code
Resident Monitor Zone Response
Resident Response Zone Response
General Monitor Zone Response
General Response Zone Response
Local Alarm

- 26 -

Lyric Controller Installation and Reference Guide

System Operation

*If APL is enabled, AlarmNet 360TM will generate a special comm. fail message (E316) if it does not hear from a unit within 15
minutes after a delayed alarm is delivered. This message is meant to alert the Central Station that the system has been
tampered with and may have been compromised.
CID Code
1401
3000
3001
3100
3101
3200
3201
3300
3301
3302
3400
3401
3402
3403
3404
3405
3406
3407
3408
3409
3410
3411
3412
4000
4001
4002
4003

Definition

Event Log Display
Local Alarm
Multilevel Switch Off
Multilevel Switch On
Multilevel Switch Off
Multilevel Switch On

Local Alarm
Binary Switch Off
Binary Switch On
Multi Level Switch Change Level (Off)
Multi Level Switch Change Level (On)
Garage Door Close
Garage Door Open
Door Lock Unlocked
Door Lock Locked
Door Lock Jammed
Thermostat Mode Off
Thermostat Mode Heat
Thermostat Mode Cool
Thermostat Mode Auto
Thermostat Mode Aux /Em Heat
Thermostat Fan Mode Auto
Thermostat Fan Mode Manual On
Thermostat Fan Mode Circulate
Thermostat Set Heat Point
Thermostat Set Cool Point
Thermostat Hold
Thermostat No Scheduling
Thermostat Normal Mode
Voice Command Success
Voice Command Failed
Voice Trigger Success
Voice Trigger Fail

Door Unlocked
Door Locked

Central Station Messages
The following messages are sent by the controller internal cellular or WiFi devices for the conditions listed
below.
Alarm Condition
Power On / Reset
Primary Communication Path Supervision
Secondary Communication Path Supervision
Test

Alarm Code
E33900950
E350C0951
E350C0952
555555559

Restore Code
R350C0951
R350C0952

The controller sends its own general code (E353) for a trouble condition. Additionally, it sends tamper trouble
(E341), tamper alarm (E145), power loss (E301) and low battery (E302) messages.

- 27 -

Lyric Controller Installation and Reference Guide

Testing the System
TO THE INSTALLER
Regular maintenance and inspection (at least annually) by the installer and frequent testing by the user are
vital to continuous satisfactory operation of any alarm system.
The installer should assume the responsibility of developing and offering a regular maintenance program to
the user as well as acquainting the user with the proper operation and limitations of the alarm system and its
component parts. Recommendations must be included for a specific program of frequent testing (at least
weekly) to ensure the system’s proper operation at all times.

Test Modes
Modes
The “Test” button provides access to the following functions and test modes:
Option
Walk Test
RF Sniffer Test
Go-No-Go Test
Diagnostics
Zone Discovery
Install Cell
System
Information
Install Backup
Battery

Function
Refer to the User Manual for additional information
Refer to the Installing Wireless Zones section of this manual for additional information.
Refer to the Installing Wireless Zones section of this manual for additional information.
Provides access to the Reboot Feature. Refer to the paragraph in this section for additional
information regarding this feature.
Provides access to the Zone Discovery mode. Refer to the paragraph in this section for
additional information regarding the Zone Discovery feature.
User feature that allow the Master User to install or replace a Communications Module.
Refer to the User Guide (p/n 800-18078) for additional information.
System Information is displayed. Select OK to return to the previous screen.
User feature that allow the Master User to replace the backup battery. Refer to the User
Guide (p/n 800-18078) for additional information.

Testing the System
After installation is completed, the security system should be carefully tested, as follows:
1.

With the system in the disarmed state, check that all zones are intact. If the “ready” LED or “Home” button
is not lit, select the Zones icon to display the faulted zone(s). If necessary, restore faulted zone(s) so that
the “ready” LED or “Home” button lights. Fault and restore every sensor individually to assure that it is
being monitored by the system.

Armed System Test
Alarm messages will be sent to the Central Station during the following tests 1 and 2.
Station in advance that tests will be in progress.
1.
2.

3.
4.

Notify the Central

Arm the system and fault one or more zones. After 15 seconds (if optional dialer delay is selected), silence
alarm sounder(s) by disarming the system. Check entry/exit delay zones.
Check the keypad-initiated alarms that are in the system by selecting the Panic key. If the system has been
programmed for audible emergency, the keypad will emit a steady alarm sound, and “ALARM” and zone
number will be displayed. Silence the alarm by entering the Security Code.
If the system has been programmed for silent emergency, there will be no audible alarms or displays, but a
report will be sent to the Central Station.
Notify the Central Station when all tests are finished, and verify results with them.
To test the wireless part of the system and the RF receiver, perform the two additional tests described in
the Installing Wireless Zones section: Sniffer mode and Go/No Go Test.

Note:

System Test mode and Go/No Go Test will be automatically terminated after 3-1/2 to 4 hours if the
installer or user does not manually terminate it. This ensures that fire and panic zones will not remain
disabled. However, Sniffer mode does not automatically expire. You must manually exit Sniffer mode by
selecting the Home key and entering the Master Code, to return to normal operation. During the final 5
minutes the system will emit double beeps indicating that the end of Test mode is nearing.

- 28 -

LYNX Touch Installation and Setup Guide

Testing the System (Continued)
Zone Discovery Mode
Zone Discovery mode requires Installer supervision when in use. The system is not fully operational
for fire or life
lif e safety while Zone Discovery Mode is active.
Zone discovery mode can be used to remotely view all zones that have been programmed in the system for
operation. The zones must have a response type programmed and in the case of RF zones, must also have a
serial number programmed. All zones programmed (except for duress) will be displayed.

Enter Zone Discovery
1.

With the System in the Installer Programming mode, select the “Test” button and then select the “Zone
Discovery” button. The “Zone Discovery” button will be highlighted indicating that the mode is active.

Exit Zone Discovery
1.

Select the Home key and enter the Master Code. If you do not exit Zone Discovery mode manually, the
system will automatically exit zone discovery mode in approximately 1-4 minutes dependent upon the
number of zones that are programmed. The system beeps once and returns to the home screen.

Rebooting the System
The Reboot function allows you to restart the system if required. To reboot the system perform the following:
1.
2.
3.

With the System in the Installer Programming mode, select the “Test” button and then select the
“Diagnostics” button.
The system advances to the next screen. Select the “Reboot” button. A confirmation screen appears.
Select “Yes”. The system will restart.

Note: After the reboot sequence is complete it is recommended that you perform a “Walk Test” to verify that
all transmitters are operational in the system.
.

- 29 -

Lyric Controller Installation and Reference Guide

Programming
Programming Default Values
Program Function
Installer Code
System Type
RF Jam
RF House Code
Two Way Voice
Events - Log All
Events - Log Alarm
Events - Log Bypass
Events - Log Open/Close
Events - Log Trouble
Non Security
Remote Access Serial
Multi Mode Serial
Date Time
Calendar
Enter Time
Time Zone
Day Light Savings time
Start Month
Start Week
End Month
End Week
Communicator
Communications Path
APL
City ID
CS ID
Sub ID
Supervision
Old Alarm Time
Remote Acc. Comm.
Multi Mode Comm.
WiFi Fault Time (min)
Use DHCP
GSM Fault Time
GSM Rollover
GSM 24 Hour Test
NIC IP Address
Subnet Mask
Gateway IP Address
DNS Server IP Address
Zones
Keys
Reporter
Report Selection
Arm Away
Arm Stay
Disarm
Exit Error
Recent Closing
Event Log Full
Trouble

Configuration 1
4112

Configuration 2
4112

Configuration 3
4112

Configuration 4
4112

RF Jam Log
0
Disabled
Press to Log All
Enabled
Enabled
Enabled
Enabled
Enabled
Disabled
Disabled

RF Jam Log
0
Disabled
Press to Log All
Enabled
Enabled
Enabled
Enabled
Enabled
Disabled
Disabled

RF Jam Log
0
Disabled
Press to Log All
Enabled
Disabled
Disabled
Enabled
Disabled
Disabled
Disabled

RF Jam Log
0
Disabled
Press to Log All
Enabled
Disabled
Disabled
Enabled
Disabled
Disabled
Disabled

January 1, 2013
12:00 PM
Eastern (EST)
Yes
March
Second
November
First

January 1, 2013
12:00 PM
Eastern (EST)
Yes
March
Second
November
First

January 1, 2013
12:00 PM
Eastern (EST)
Yes
March
Second
November
First

January 1, 2013
12:00 PM
Eastern (EST)
Yes
March
Second
November
First

WiFi
WiFi
WiFi
WiFi
Disabled
Disabled
Disabled
Disabled
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
24 Hours
24 Hours
24 Hours
24 Hours
10 Minutes
10 Minutes
10 Minutes
10 Minutes
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
60
60
60
60
Yes
Yes
Yes
Yes
60
60
60
60
No
No
No
No
No
No
No
No
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
See Zone Programming Default Configurations
See Zone Programming Default Configurations

Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled

Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled

- 30 -

Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled

Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled

Lyric Controller Installation and Reference Guide

Programming Default Values
Values (Continued)
Program Function
Trouble Restore
Alarm Restore
Alarm Cancel
Test
Test Restore
Bypass
Bypass Restore
AC Loss
AC Loss Restore
Low Battery
Low Battery Restore
RF Low Battery
RF Low Battery Restore
Options
Number of Reports
Alarm Report Delay
First Report Offset
Report Frequency
Sounder
Burglary Alarm Sound
Burglary Bell Timeout
Fire Bell Timeout
Arm Confirm
System Settings
Entry Delay 1
Entry Delay 2
Exit Delay
Backlight Timeout
Quick Arm
Quick Exit
Restart Exit Time
Force Bypass
Exit Warning
Auto Stay Arming
Lack Of Usage Notify
Power-Up In Previous
Display Alarm Cancel
Display Exit Time
(A) Cross Zone Delay
(A) Cross Zone 1
(A) Cross Zone 2
(B) Cross Zone Delay
(B) Cross Zone 1
(B) Cross Zone 2
(C) Cross Zone Delay
(C) Cross Zone 1
(C) Cross Zone 2
(D) Cross Zone Delay
(D) Cross Zone 1
(D) Cross Zone 2

Configuration 1
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled

Configuration 2
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled

Configuration 3
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled

Configuration 4
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled

2 Reports
30 Sec.
6 Hrs
Never

2 Reports
30 Sec.
12 Hrs
30 Days

2 Reports
30 Sec.
12 Hrs
Never

2 Reports
30 Sec.
12 Hrs
Never

Yes
4 Minutes
4 Minutes
RF Keyfob

Yes
4 Minutes
4 Minutes
RF Keyfob

Yes
4 Minutes
4 Minutes
RF Keyfob

Yes
4 Minutes
4 Minutes
RF Keyfob

30 Seconds
30 Seconds
60 Seconds
30 Seconds
Yes
Yes
Yes
No
Yes
Yes
Disabled
Yes
Yes
Yes
None
Disabled
Disabled
None
Disabled
Disabled
None
Disabled
Disabled
None
Disabled
Disabled

30 Seconds
30 Seconds
60 Seconds
30 Seconds
Yes
Yes
Yes
No
Yes
Yes
Disabled
Yes
Yes
Yes
None
Disabled
Disabled
None
Disabled
Disabled
None
Disabled
Disabled
None
Disabled
Disabled

30 Seconds
30 Seconds
60 Seconds
30 Seconds
Yes
Yes
Yes
No
Yes
Yes
Disabled
Yes
Yes
Yes
None
Disabled
Disabled
None
Disabled
Disabled
None
Disabled
Disabled
None
Disabled
Disabled

30 Seconds
30 Seconds
60 Seconds
30 Seconds
Yes
Yes
Yes
No
Yes
Yes
Disabled
Yes
Yes
Yes
None
Disabled
Disabled
None
Disabled
Disabled
None
Disabled
Disabled
None
Disabled
Disabled

- 31 -

Lyric Controller Installation and Reference Guide

Programming Default Values (Continued)
Program Function
Z-Wave
Z-Wave
Temperature
Language
Installer Language
User Language
RF Keypad

Configuration 1

Configuration 2

Configuration 3

Configuration 4

Enabled
Fahrenheit

Enabled
Fahrenheit

Enabled
Fahrenheit

Enabled
Fahrenheit

English
English

English
English
English
English
See Zone Programming Default Configurations

English
English

Zone Assignment/Alarm Response Types for Configuration 1
Zone
Loop
Number Number
1
--2
--3
2
4
2
5
2
6
1
127
1
128
1
129
1
130
1
131
3
132
2
133
4
134
1
135
3
136
2
137
4
138
1
280
--281
--282
--283
--284
--285
--286
--287
--288
--289
--290
--291
--850
--851
--852
--853
--854
--855
--856
--857
--995
--996
--998
--999
---

Device Type

Response Type

New
New
Door
Door
Window
Motion Sensor
New
New
New
New
4 Button
4 Button
4 Button
4 Button
4 Button
4 Button
4 Button
4 Button
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Fire
Medical
Local Alarm
Police

Not Used
Not Used
Entry Exit 1
Entry Exit 1
Perimeter
Interior With Delay

Not Used
Not Used
Not Used
Not Used
Arm Away
Disarm
Arm Stay
No Response
Arm Away
Disarm
Arm Stay
No Response
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Day/Night
Day/Night
Day/Night
Day/Night
Day/Night
Day/Night
Day/Night
Day/Night
Fire No Verification

Not Used
Local Alarm
24-Hour Silent

Alarm
Report
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
Yes
Yes
Yes
No
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes

- 32 -

Chime

Supervision

Disabled
Disabled
Standard
Standard
Standard
Disabled
Standard
Standard
Standard
Standard
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled

End of Line
End of Line
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Button
Button
Button
Button
Button
Button
Button
Button
High Temp
Low Temp
High Temp
Low Temp
High Temp
Low Temp
High Temp
Low Temp
High Temp
Low Temp
High Temp
Low Temp
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Panic Trigger
Panic Trigger
Panic Trigger
Panic Trigger

Arm
Night
n/a
n/a
n/a
n/a
n/a
No
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a

Zone Descriptor
n/a
n/a
Front
Back
n/a
n/a
Main
Main
Main
Main
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a

Lyric Controller Installation and Reference Guide

Programming Default Values
Zone Assignment/Alarm Response Types for Configuration 2
Zone
Loop
Number Number
1
--2
--3
2
4
2
5
2
6
1
7
1
127
1
128
1
129
1
130
1
131
3
132
2
133
4
134
1
135
3
136
2
137
4
138
1
280
--281
--282
--283
--284
--285
--286
--287
--288
--289
--290
--291
--850
--851
--852
--853
--854
--855
--856
--857
--995
--996
--998
--999
---

Device Type
New
New
Door
Door
Door
Motion Sensor
Smoke Detector
New
New
New
New
4 Button
4 Button
4 Button
4 Button
4 Button
4 Button
4 Button
4 Button
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Fire
Medical
Local Alarm
Police

Alarm
Report
Not Used
Yes
Not Used
Yes
Entry Exit 1
Yes
Entry Exit 1
Yes
Entry Exit 1
Yes
Interior With Delay
Yes
Fire No Verification
Yes
Not Used
No
Not Used
No
Not Used
No
Not Used
No
Arm Away
Yes
Disarm
Yes
Arm Stay
Yes
No Response
No
Arm Away
Yes
Disarm
Yes
Arm Stay
Yes
No Response
No
Monitor
Yes
Monitor
Yes
Monitor
Yes
Monitor
Yes
Monitor
Yes
Monitor
Yes
Monitor
Yes
Monitor
Yes
Monitor
Yes
Monitor
Yes
Monitor
Yes
Monitor
Yes
Yes
Day/Night
Yes
Day/Night
Yes
Day/Night
Yes
Day/Night
Yes
Day/Night
Yes
Day/Night
Yes
Day/Night
Yes
Day/Night
Fire No Verification
Yes
24-Hour Auxiliary
Yes
Local Alarm
Yes
24-Hour Audible
Yes
Response Type

- 33 -

Chime

Supervision

Disabled
Disabled
Standard
Standard
Standard
Disabled
Disabled
Standard
Standard
Standard
Standard
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled

End of Line
End of Line
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Button
Button
Button
Button
Button
Button
Button
Button
High Temp
Low Temp
High Temp
Low Temp
High Temp
Low Temp
High Temp
Low Temp
High Temp
Low Temp
High Temp
Low Temp
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Panic Trigger
Panic Trigger
Panic Trigger
Panic Trigger

Arm
Night
n/a
n/a
n/a
n/a
n/a
No
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a

Zone Descriptor
n/a
n/a
Front
Back
Garage
n/a
n/a
Main
Main
Main
Main
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a

Lyric Controller Installation and Reference Guide

Zone Programming Default Values
Zone Assignment/Alarm Response Types for Values 3 and 4
Zone
Loop
Number Number
1
--2
--3
2
4
2
5
2
6
2
7
2
8
2
9
1
10
1
127
1
128
1
129
1
130
1
131
3
132
2
133
4
134
1
135
3
136
2
137
4
138
1
280
--281
--282
--283
--284
--285
--286
--287
--288
--289
--290
--291
--850
--851
--852
--853
--854
--855
--856
--857
--995
--996
--998
--999
---

Device Type

Response Type

New
New
Door
Door
Window
Window
Window
Window
Motion Sensor
Smoke Detector
New
New
New
New
4 Button
4 Button
4 Button
4 Button
4 Button
4 Button
4 Button
4 Button
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Fire
Medical
Local Alarm
Police

Not Used
Not Used
Entry Exit 1
Entry Exit 1
Perimeter
Perimeter
Perimeter
Perimeter
Interior With Delay
Fire No Verification

Not Used
Not Used
Not Used
Not Used
Arm Away
Disarm
No Response
No Response
Arm Away
Disarm
No Response
No Response
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Day/Night
Day/Night
Day/Night
Day/Night
Day/Night
Day/Night
Day/Night
Day/Night
Fire No Verification

Not Used
Local Alarm
24-Hour Silent

Alarm
Report
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
Yes
Yes
Yes
No
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes

- 34 -

Chime

Supervision

Disabled
Disabled
Standard
Standard
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Standard
Standard
Standard
Standard
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled

End of Line
End of Line
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Button
Button
Button
Button
Button
Button
Button
Button
High Temp
Low Temp
High Temp
Low Temp
High Temp
Low Temp
High Temp
Low Temp
High Temp
Low Temp
High Temp
Low Temp
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Panic Trigger
Panic Trigger
Panic Trigger
Panic Trigger

Arm
Night
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
No
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a

Zone Descriptor
n/a
n/a
Front
Back
n/a
n/a
n/a
n/a
n/a
n/a
Main
Main
Main
Main
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a

General Response

Fire With Verification

General Monitor

x
x
x
x
x
x

x
x
x
x
x
x
x

Motion Sensor
x
x
x
x
x

Glass Break

Smoke Detector
x
x
x
x
x
x
x

Heat Sensor
x

Temperature

Other
x

Environmental
x

x
x
x
x
x

x

x
x

x

x
x

x
x
x

Carbon Monoxide Detector

Fire

x
x

- 35 x
x
x

x

Flood

Medical
x

Police

x
x

x

x

x

x

x

x

x
x

x
x

x

x

Local Alarm
x

x
x
x
x
x

Bell

x

Garage Door

x
x
x

x
x

x
x
x

Local Alarm

Trouble

Garage Monitor

Garage

Silent Burglary

No Response

Disarm

Arm Away

Arm Stay

Not Used

Monitor

24 Hour Silent

24 Hour Audible

24 Hour Auxiliary

Carbon Monoxide

Interior With Delay

Resident Response

Fire No Verification

Resident Monitor

x

Interior Follower

Perimeter

Window
Day/Night

Entry Exit 2

Device Type
Door
Entry Exit 1

Response Type

Lyric Controller Installation and Reference Guide

Zone Response Type Matrix

x

x
x

x

x
x

Lyric Controller Installation and Reference Guide

Regulatory
Regula tory Agency Statements
Federal Communications Commission (FCC
( FCC)
FCC) Part 15
The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's
Manual. Unauthorized changes or modifications could void the user's authority to operate the equipment.

CLASS B DIGITAL DEVICE STATEMENT
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC
Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This
equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions,
may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a
particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by
turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.




This Class B digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.

FCC IC Statement
This device complies with Part 15 of FCC Rules and RSS-210 of Industry Canada. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and (2) This device must accept any interference received, including interference
that may cause undesired operation.
Cet appareil est conforme à la partie 15 des règles de la FCC & de RSS-210 des Industries Canada. Son fonctionnement est soumis aux
conditions suivantes: (1) Cet appareil ne doit pas causer d' interferences nuisibles. (2) Cet appareil doit accepter toute interference
reçue y compris les interferences causant une reception indésirable.

RF Exposure Warning

!

The antenna(s) used for this transmitter must be installed to provide a separation distance of at least 7.8 in (20 cm)
from all persons and must not be co-located or operated in conjunction with any other transmitter except in
accordance with FCC multi-transmitter product procedures.

Mise en Garde
Exposition aux Frequences Radio: L'antenne (s) utilisée pour cet émetteur doit être installée à une distance de
séparation d'au moins 7,8 pouces (20 cm) de toutes les personnes.

IMPORTANT NOTES
NOTE S ABOUT EXTERNAL ANTENNAS
If an external cellular radio antenna is used, the antenna may be installed or replaced ONLY by a professional
installer.
TO THE INSTALLER
For the Lyric-3G, the external antenna must not exceed a maximum directional gain (including cable loss) of 3.2
dBi at 850 MHz and 2.3 dBi at 1900 MHz.
For the Lyric-CDMA, the external antenna must not exceed a maximum directional gain (including cable loss) of
8.5 dBi at 850 MHz and 4.1 dBi at 1900 MHz.

- 36 -

Lyric Controller Installation and Reference Guide
WARNING
THE LIMITATIONS OF THIS ALARM SYSTEM
While this System is an advanced design security system, it does not offer guaranteed protection against
burglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to
compromise or failure to warn for a variety of reasons. For example:

Intruders may gain access through unprotected openings or have the technical sophistication to bypass an alarm
sensor or disconnect an alarm warning device.

Intrusion detectors (e.g., passive infrared detectors), smoke detectors, and many other sensing devices will not
work without power. Battery-operated devices will not work without batteries, with dead batteries, or if the
batteries are not put in properly. Devices powered solely by AC will not work if their AC power supply is cut off for
any reason, however briefly.

Signals sent by wireless transmitters may be blocked or reflected by metal before they reach the alarm receiver.
Even if the signal path has been recently checked during a weekly test, blockage can occur if a metal object is
moved into the path.

A user may not be able to reach a panic or emergency button quickly enough.

While smoke detectors have played a key role in reducing residential fire deaths in the United States, they may not
activate or provide early warning for a variety of reasons in as many as 35% of all fires, according to data
published by the Federal Emergency Management Agency. Some of the reasons smoke detectors used in
conjunction with this System may not work are as follows. Smoke detectors may have been improperly installed
and positioned. Smoke detectors may not sense fires that start where smoke cannot reach the detectors, such as
in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on
another level of a residence or building. A second floor detector, for example, may not sense a first floor or
basement fire. Finally, smoke detectors have sensing limitations. No smoke detector can sense every kind of fire
every time. In general, detectors may not always warn about fires caused by carelessness and safety hazards like
smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical
circuits, children playing with matches, or arson. Depending on the nature of the fire and/or location of the smoke
detectors, the detector, even if it operates as anticipated, may not provide sufficient warning to allow all
occupants to escape in time to prevent injury or death.

Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as diagrammed in their
installation manual. Passive Infrared Detectors do not provide volumetric area protection. They do create multiple
beams of protection, and intrusion can only be detected in unobstructed areas covered by those beams. They
cannot detect motion or intrusion that takes place behind walls, ceilings, floors, closed doors, glass partitions, glass
doors, or windows. Mechanical tampering, masking, painting or spraying of any material on the mirrors, windows
or any part of the optical system can reduce their detection ability. Passive Infrared Detectors sense changes in
temperature; however, as the ambient temperature of the protected area approaches the temperature range of
90° to 105°F (32° to 40°C), the detection performance can decrease.

Alarm warning devices such as sirens, bells or horns may not alert people or wake up sleepers if they are located
on the other side of closed or partly open doors. If warning devices are located on a different level of the
residence from the bedrooms, then they are less likely to waken or alert people inside the bedrooms. Even persons
who are awake may not hear the warning if the alarm is muffled by noise from a stereo, radio, air conditioner or
other appliance, or by passing traffic. Finally, alarm warning devices, however loud, may not warn hearingimpaired people.

Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be out of
service or temporarily out of service. Telephone lines are also subject to compromise by sophisticated intruders.

Even if the system responds to the emergency as intended, however, occupants may have insufficient time to
protect themselves from the emergency situation. In the case of a monitored alarm system, authorities may not
respond appropriately.

This equipment, like other electrical devices, is subject to component failure. Even though this equipment is
designed to last as long as 10 years, the electronic components could fail at any time.
The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate
maintenance. This alarm system should be tested weekly to make sure all sensors and transmitters are working
properly. The security keypad (and remote keypad) should be tested as well.
Wireless transmitters (used in some systems) are designed to provide long battery life under normal operating
conditions. Longevity of batteries may be as much as 4 to 7 years, depending on the environment, usage, and the
specific wireless device being used. External factors such as humidity, high or low temperatures, as well as large
swings in temperature, may all reduce the actual battery life in a given installation. This wireless system, however, can
identify a true low battery situation, thus allowing time to arrange a change of battery to maintain protection for that
given point within the system.
Installing an alarm system may make the owner eligible for a lower insurance rate, but an alarm system is not a
substitute for insurance. Homeowners, property owners and renters should continue to act prudently in protecting
themselves and continue to insure their lives and property.
We continue to develop new and improved protection devices. Users of 7
alarm systems owe it to themselves and their loved ones to learn about these developments.

- 37 -

Lyric Controller Installation and Reference Guide

Agency Notices
1.

2.
3.
4.
5.

For Residential Burglar Alarm installations with line security, total exit delay time must not exceed 60
seconds. For Burglar Alarm installations without line security, total exit delay time must not exceed 120
seconds.
Periodic testing must be at least every 24 hours.
Remote downloading without an alarm company technician on-site (unattended downloading) is not
permissible for ETL installations.
Auto-disarming is not a Listed feature.
As SIA limits for delay of alarm reporting and sounding can exceed UL Standard limits for commercial and
residential applications, the following UL requirements per UL681 are provided:
The maximum time that a control unit shall be programmed to delay the transmission of a signal to a
remote monitoring location, or to delay the energizing of a local alarm sounding device to permit the
alarm system user to enter and disarm the system, or to arm the system and exit shall not exceed:
a) 60 seconds for a system with standard line security or encrypted line security,
b) 120 seconds for a system without standard line security or encrypted line security, or
c) 120 seconds for a system that does not transmit an alarm signal to a remote monitoring location.

SIA Quick Reference Guide
Programming Section

Feature

Range

Shipping Default

SIA Requirement

Installation and Setup Gui
Guide
de or Programming Guide
Exit Error
Enabled or Disabled
Reporter/
Reporter
Report Selection
Recent Closing
Enabled or Disabled

Enabled
Enabled

Enabled
Enabled

Alarm Cancel

Enabled or Disabled

Enabled

Enabled

Number of
Reports

1 to 6 Reports

2 Reports

2 Reports

Alarm Report
Delay (Abort
Window)

15, 30 and 45 seconds

30 seconds

30 seconds*

Entry Delay # 1

None, 15, 30, 45, 60 and
90 seconds and 2, 3 or
4
minutes
None,
15, 30, 45, 60 and

30 seconds

30 seconds minimum

30 seconds

30 seconds minimum

Reporter/Options
Reporter

System Settings

Entry Delay # 2

60 Seconds

45 seconds minimum

Restart Exit Time

90 seconds and 2, 3 or
4
minutes
45,
60, 90 seconds and
2 minutes
Enabled or Disabled

Yes (Enabled)

Enabled

Exit Warning

Not selectable

Always enabled

Enabled

Auto Stay
Arming

Enabled or Disabled

Yes (Enabled)

Enabled

Cross Zone Delay

30 seconds and 2
minutes (in 30 second
increments), 3 minutes
and
minutes
Zone4Type
“Fire with

None (Disabled)

Enabled and two zones
programmed

Disabled

Disabled

Disabled

Disabled

n/a

n/a

Disabled

Disabled

Exit Delay

Zones

User Guide
User Functions/
User Access
System Functions/
Testing the System**

Fire Alarms

Verification” must be
selected for Fire Zone
95
Duress

System Test
Communications

Duress Code is
Programmed by Master
User as User 16
System tests provided
as a User Function
While the system is in
Test mode, no alarm
reports are sent to the
Central Station

* Combined Entry Delay and Alarm Report Delay (Abort Window) should not exceed 1 minute.
** Refer to the User Guide for procedures on Testing the System.

- 38 -

Lyric Controller Installation and Reference Guide

Specifications
Lyric Controller Series Security Controls
Physical:
Dimensions:
8.5” (216mm) W x 6.65” (169mm) H x 1.3” (33mm) D
Electrical:
Voltage Input:
9 Vdc from plug-in 2.7A power supply
Rechargeable Backup Battery: Nickel-metal hydride battery pack rated at 7.2 Vdc
Communication:
Formats Supported:
ADEMCO Contact ID® Reporting, 10 characters/sec., DTMF (TouchTone) Data
Tones, 1400/2300Hz Handshake, 1400Hz Kissoff.
SIA/DCS Format, 2225Hz Handshake, Data Tones, 2025/2235Hz, baud
Hardwire Zones
2K ohms, End of Line Resistor (EOLR), 200 ohms max wire resistance, dry
Zones:
contacts only
Trigger Output:
1K ohms to ground when closed (output low) 3ma

- 39 -

Lyric Controller Installation and Reference Guide

Glossary
AES – Advanced Encryption Standard
APL – Advanced Protection Logic
dBM – decibels milliwatt (power ratio)
CDMA - Code Division Multiple Access is a channel access method used by various radio communication
technologies that allows many users to occupy the same time and frequency allocations in a given band/space.
DHCP – Dynamic Host Configuration Protocol, which provides a mechanism for allocating IP addresses
dynamically so that addresses can be reused when hosts no longer need them.
DNS – Domain Name System, which is a distributed hierarchical naming system used to resolve domain names
(e.g., www.yahoo.com) into numerical IP addresses (e.g., 204.17.25.1).
Ec/Io – Signal to noise ratio of the current channel for CDMA (Measured in dB).
Eb/No – Signal to noise ratio of the current channel for UTMS (3G) (Measured in dB).
ESN – Electronic Serial Number (32 bit number that identifies a CDMA device)
Gateway IP Address – A gateway (sometimes called a router) is a computer and/or software used to connect
two or more networks (including incompatible networks) and translates information from one network to the
other. The Gateway IP address is the IP address for the gateway.
GPRS – General Packet Radio Service
GSM – Global System for Mobile communications, which is an international standard for digital mobile phone
systems used for cellular communication.
HSDPA – High-Speed Downlink Packet Access
HSPA – High-Speed Packet Access
ICCID – Integrated Circuit Card Identifier (SIM Card serial number)
IMEI – International Mobile Equipment Identity number
IP – Internet Protocol
IP Address – A unique number consisting of four parts separated by periods, sometimes called a "dotted quad.,"
for example: 204.17.29.11, assigned to every computer/workstation connected to the Internet. IP numbers can
be "static" (assigned and unchanging) or "dynamic," assigned via DHCP at each and every startup.
ISP – Internet Service Provider
KBPS – Kilobits per second
MAC ID – Media Access Code; located on the module label.
MEID – Mobile Equipment Identifier (56 bit number that identifies a CDMA device)
NIC – Network Interface Card
RSCP – Received Signal Code Power (Ratio of RSSI and Ec/No)
RSSI – Received Signal Strength Indication
SCID – SIM Card ID
Subnet Mask – A Subnet is a portion of a network that shares a network address with other portions of the
network, and is distinguished by a subnet number. The Subnet Mask is a 32-bit address mask used in IP to
indicate the bits of an IP address that are being used for the subnet address.
UMTS – Universal Mobile Telecommunications Service
WEP – Wired Equivalent Privacy
WPA – WiFi Protected Access
WPS – WiFi Protected Setup

- 40 -

Lyric Controller Installation and Reference Guide

Contacting Technical Support
PLEASE, before you call Technical Support,
Support , be sure you:

READ THE INSTRUCTIONS!

Check all wiring connections.

Determine that the power supply and/or backup battery are supplying proper voltages.

Verify your programming information where applicable.

Note the proper model number of this product, and the version level (if known) along with any
documentation that came with the product.

Note your Honeywell customer number and/or company name.

Having this information handy will make it easier for us to serve you quickly and effectively.

Technical Support: ...................................................................................................... 1-800-645-7492 (8 a.m.-10 p.m. E.S.T.)
MyWebTech: ..................................................................... http:// www.honeywell.com/security/hsc/resources/MyWebTech

- 41 -

Lyric Controller Installation and Reference Guide

– Index –
24-Hour Silent .............................................................. 22
300-03864-3PIN .......................................................... 7
300-03866 ..................................................................5, 7
300-07332US .............................................................. 10
5800 Series Transmitter Loop Numbers ..........14
5800 Series Transmitters ........................................ 13
5816 ................................................................................... 13
5834-2 .............................................................................. 13
5834-4.............................................................................. 13
5878 .................................................................................. 13
AC Power ....................................................................... 10
AC Power Loss .............................................................. 7
ADEMCO Contact ID ................................................39
Armed System Test ................................................... 28
Audio Alarm Verification (Two-Way Voice
Feature)...................................................................... 25
Babysitter Code .......................................................... 22
Backup Battery .................................................... 10, 39
Button Transmitters ................................................... 13
CDMA Cellular Communications Module ........... 11
Communication Modules .......................................... 11
Contact ID Event Log Codes ................................26
Contact ID Reporting ...............................................39
Contacting Technical Support ...............................41
Dialer Delay................................................................... 28
DIP Switches ................................................................. 13
Duress Code ................................................................. 22
Enter Installer Programming Mode ..................... 18
Enter/Change The Master Code .......................... 22
Entry Delay .................................................................. 20
Entry/Exit Burglary .................................................. 20
Exit Delay................................................. 17, 20, 28, 38
Exit Programming Mode ..........................................19
GSM Cellular Communications Module ............... 11
Home Screen .................................................................16
House ID Code.............................................................. 13
House Identification ................................................... 13
Installer Code ............................................................... 22
Installer Tools Menu Screen .................................... 18
Installing Wireless Zones .........................................14
Key/Touchscreen Operation ................................. 22
Keysfobs ......................................................................... 13
Liquid Crystal Display (LCD) Touch-Screen .... 15
Loading Factory Defaults ........................................19
LYRIC-3G ......................................................................... 11
LYRIC-CDMA .................................................................. 11
Master Code ................................................................. 22
Master Security Code ............................................... 22

User Security Code ................................................... 22
Master User Tools Screen ....................................... 17
Memory Of Alarm ...................................................... 22
Navigating Menus ................................................. 15, 17
Navigation Keys .......................................................... 16
News ................................................................................. 16
Operator Commands ............................................... 25
Panic Key/Icons.......................................................... 22
Plug-In Power Supply ............................................... 10
Range ............................................................................... 13
Reboot ............................................................................ 29
Rebooting The System ............................................ 29
Regulatory Agency Statements .......................... 36
Reset Master User Code ......................................... 23
RF House Code ............................................................ 13
Secondary User Codes ............................................ 22
Security Codes ............................................................ 22
Security Screen............................................................ 17
Programming Default Tables .................. 30, 31, 32
SiXFOB ............................................................................ 13
SiX™ Series Transmitters ......................................... 13
Sniffer Mode ................................................................. 28
Specifications .............................................................. 39
Super High Capacity Battery .................................. 11
Supervised RF .............................................................. 13
System Features ...................................................... 5, 6
System Operation...................................................... 22
System Standby Screen ........................................... 18
Technical Support ...................................................... 41
Test Modes ................................................................... 28
Testing The System ........................................... 28, 29
Touch-Screen Display ............................................... 15
Traffic ............................................................................... 16
Transmitter Battery Life .......................................... 13
Transmitter Input Type ............................................ 13
Transmitter Loop Numbers .................................... 14
Transmitter Supervision ........................................... 13
Unsupervised Button ................................................ 13
Unsupervised RF ......................................................... 13
Wall Mounting ......................................................... 8, 10
Wireless Keyfobs ........................................................ 13
Wireless Zones............................................................. 13
World Wide Web Address...................................... 41
Zone Discovery........................................................... 29
Zone Programming Default Values.................... 34
Zone Response Type Definitions ........................ 20
Zone Response Type Matrix ................................. 35

- 42 -

Lyric Controller Installation and Reference Guide

THIS EQUIPMENT SHOULD BE INSTALLED IN ACCORDANCE
WITH THE NATIONAL FIRE PROTECTION ASSOCIATION
STANDARDS ANSI/NFPA 70 NATONAL ELECTRIC CODE AND
NFPA 72 NATIONAL FIRE ALARM CODE, CHAPTER 2
(NATIONAL FIRE PROTECTION ASSOC., BATTERY MARCH
PARK, QUINCY, MA 02169). PRINTED INFORMATION
DESCRIBING PROPER INSTALLATION, EVACUATION
PLANNING AND REPAIR SERVICE IS TO BE PROVIDED WITH
THIS EQUIPMENT.

LYRIC ALSO COMPLIES WITH THE FOLLOWING:
CANADIAN STANDARDS ASSOCIATION (CSA)
C22.1, CANADIAN ELECTRICAL CODE, PART 1,
SAFETY STANDARD FOR ELECTRICAL
INSTALLATIONS AND CAN/ULC-S540
INSTALLATION OF RESIDENTIAL FIRE WARNING
SYSTEMS.

THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES.
OPERATION IS SUBJECT TO THE FOLLOWING TWO
CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE
HARMFUL INTERFERENCE, AND (2) THIS DEVICE
MUST ACCEPT ANY INTERFERENCE RECEIVED,
INCLUDING INTERFERENCE THAT MAY CAUSE
UNDESIRED OPERATION.

NOTE: THE HARD WIRE ZONES CANNOT BE USED AS FIRE ZONES.
USB PORT
POWER SUPPLY
(300-07332US)

HARD
WIRED
ZONE

2K OHM
EOLR

HARD
WIRED
ZONE

2K OHM
EOLR

GND

+9VDC

GND

HWZ1

HWZ2

TERMINAL
BOARD

TAMPER

BATTERY
RECEPTACLE

EXTERNAL CELLULAR RADIO ANTENNAS MAY ONLY BE INSTALLED OR REPLACED BY A PROFESSIONAL INSTALLER
WARNING
THIS UNIT MAY BE PROGRAMMED TO INCLUDE AN ALARM
VERIFICATION FEATURE THAT WILL RESULT IN A DELAY OF THE
SYSTEM ALARM SIGNAL FROM THE INDICATED FIRE CIRCUITS.
THE TOTAL DELAY (CONTROL UNIT PLUS SMOKE DETECTORS)
SHALL NOT EXCEED 60 SECONDS. NO OTHER INITIATING
DEVICES SHALL BE CONNECTED TO THESE CIRCUITS UNLESS
APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION.

WEEKLY TESTING IS REQUIRED TO ENSURE
PROPER OPERATION OF THIS SYSTEM

THE LYRIC CONTROLLER IS COMPATIBLE WITH THE
FOLLOWING INTEGRAL RECHARGEABLE BATTERY PACKS:
P/N 300-03864-3PIN (STANDARD CAPACITY)
P/N 300-03866 (HIGH CAPACITY)

REPLACE EVERY FOUR YEARS

CIRCUIT
(ZONE)

CONTROL UNIT
DELAY-SEC

03 - 126
ZONE TYPE SUPERVISED
FIRE WITH
VERIFICATION

30 seconds

SMOKE DETECTOR
MODEL
DELAY-SEC
5806W3

10 seconds

lyric-SOC-V2

LYRIC SUMMARY OF CONNECTIONS
Notes: Connection of the fire alarm signal to a fire alarm headquarters or a Central Station shall be permitted
with the approval of the local authority having jurisdiction. The burglar alarm signal shall not be connected to a
police emergency number. The System must be checked by a qualified technician once every three years

- 43 -

SUPPORT & WARRANTY
For the latest documentation and online support information, please go to:
https://mywebtech.honeywell.com/
For the latest warranty information, please go to:
www.honeywell.com/security/hsc/resources/wa.

2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
Copyright © 2015 Honeywell International Inc.
www.honeywell.com/security

Ê800-18076XŠ
800-18076

4/15 Rev. B - DRAFT

MyWebTech

Warranty


Uploaded