Honeywell 5819WHS and 5819BRS Installation Manual



Related Products

Honeywell 5819WHS - Wireless Transmitter with Integrated Shock Sensor
Honeywell 5819WHS
Wireless Transmitter with Integrated Shock Sensor

Related Categories


Document Transcript

N7491-1V2 6/06 Rev. A

ADEMCO 5819WHS/5819BRS

SHOCK PROCESSOR TRANSMITTER

INSTALLATION AND SETUP GUIDE
GENERAL INFORMATION
The ADEMCO 5819WHS/5819BRS Shock Processor Transmitters each feature a built-in shock sensor and are intended for use only with alarm systems that support ADEMCO 5800 Series wireless devices. The built-in shock sensor is used to detect forcible attack upon the surface to which it is mounted. It is designed to protect window and door surroundings. The sensor is electrically normally closed, but, under shock conditions, goes open-circuit momentarily. The 5819 supports three unique zones, known as "loops": Loop 1 = built-in shock sensor loop, factory-wired to TB1 (normally closed) Loop 2 = built-in magnetic reed switch in conjunction with a magnet (normally closed) Loop 3 = externally wired, closed-circuit contact loop connected to TB2 The 5819WHS/BRS also has a built-in cover tamper switch that activates when the cover is removed and sends a "check" message to the control.

MOUNTING
The description that follows assumes that the unit will be mounted as shown in Diagram 1 below, with the magnet (if used) located to the left of the unit. The unit can be installed in any direction, as long as the relationship of the unit to the magnet is maintained. In addition, the arrow embossed on the built-in shock sensor must face UP when the unit is mounted. To change the shock sensor's orientation, gently push the sensor away from its mounting hole until it can rotate freely. Twist the sensor until the arrow is pointing UP when the detector is in the desired mounting position; then gently push the sensor until it is fully seated in its mounting hole. Before mounting the transmitter permanently, conduct Go/No Go tests (see control's instructions) to verify adequate signal strength. Reorient or relocate the transmitter if necessary. 1. Remove transmitter's cover by inserting the flat blade of a small screwdriver into the pry-off slot nearest to the cover's decorative ribs, and twisting the blade.

!

Do not remove the printed circuit board from its plastic case!

AREA OF SHOCK PROTECTION
Typical area of coverage is 10 -12 feet (5-6 foot radius). This can vary, depending on the type of window or other mounting surface to which the unit is mounted.

2. If you are using a wired contact loop, cut the thin "breakout" area provided at the lower edge in the case wall to allow wire entry. 3. Mount the case back to a solid surface using the two mounting holes shown in Diagram 1 below, and the panhead screws provided. 4. If you are using the unit's reed switch, mount a 5899 Magnet (obtained separately) adjacent to the alignment marks on the case (see Diagram 1 below). 5. If you are using an external contact, remove the battery (if installed) and connect a normally closed contact to TB2. NOTE: If the contact loops are not used, make no connection across the terminals.

DETAIL A DIP SWITCHES
1 ON 2 3 4 5

DETAIL C

COVER PRY-OFF POINT
DO NOT REMOVE PC BOARD FROM BACK OF CASE

TABLE 1 RESPONSE TIME SWITCH SW1 (Most Sensitive) 1mS SW2 2mS SW3 5mS SW4 10mS SW5 (Least Sensitive) 20mS DETAIL B
J5 J4 J3 J2 J1

Embossed arrow on shock sensor must point UP when unit is mounted.

MAGNET

BATTERY

MOUNTING HOLE

+

DIP SWITCHES See Detail “A” ANTENNA JUMPER PINS See Detail “B” LOOP 1 TERMINALS (Built-in shock sensor) See Detail “B” SHOCK SENSOR See Detail “C”

JUMPER PINS BUILT-IN SHOCK SENSOR TERMINALS (INPUT LOOP 1)

REED SWITCH COVER TAMPER SWITCH LOOP 3 TERMINAL (EXTENAL CONTACT LOOP)

INPUT LOOP 3

TB2

TB1

COUNT JUMPER J1 (Most Sensitive) 1 J2 2 J3 4 J4 6 J5 (Least Sensitive) 8

TABLE 2

MOUNTING HOLE
COVER HOLDING HOOKS (2) DIAGRAM 1

5819WHS-001-V1

SETTING RESPONSE TIME AND SENSITIVITY
1. Set response time using the DIP switches (use the tip of a pen/pencil). SW1 sets a response time of 1mS (milliSec.), SW5 sets a response time of 20mS. For a response time of 0.5mS, set all DIP switches to OFF (see Table 1). 2. Set the pulse count jumper (see Table 2). The pulse count is reset 3 seconds after the first pulse is detected. There is an LED on the PCB that flashes rapidly on transmission. NOTE: Make the device highly sensitive for the purpose of enrolling the shock sensor loop (TB1) into the system (turn SW. 1 on and put jumper on J1). After the device has been enrolled, adjust settings as described in steps 1 and 2 above.

Transmit from the unit when prompted, by activating any of its loops or tamper switch as follows: Loop 1: Flip the unit upside down, then right side up to activate the sensor. Loop 2: Bring the magnet close to the reed switch; then pull the magnet away to open and close the reed. Loop 3: Open and close the contact according to its instructions. You can also manually enter the unit's serial number. Test the unit after "enrolling" into the system using the control's test procedure.

BATTERY INSTALLATION/REPLACEMENT
1. Remove the transmitter's cover as described in Mounting Step 1. 2. Observe correct polarity and insert the battery provided into the battery holder (see Diagram 1 on first side). 3. Replace the cover, engage the hooks along one edge, and snap shut. Do not bend the antenna. Note: Replace with 3V Lithium battery only: Panasonic CR123A, Duracell DL123A, Sanyo CR123A, Varta CR123A, or ADEMCO 466. BATTERY CAUTION: Risk of fire, explosion, and burns. Do not recharge, disassemble, heat above 212°F (100°C), or incinerate. Dispose of used batteries promptly. Keep away from children.

"ENROLLING" THE TRANSMITTER SERIAL NUMBER
Each 5819 Shock Processor has a unique, factory-set serial number (assigned during manufacture) that must be "enrolled" by the control before usage in the system. In addition, each zone (loop) of the transmitter must also be programmed at the control panel during installation. When programming, note the following: • The battery must be installed before "enrolling." • Assign each loop to an individual zone number and assign Input Type = 3 (Supervised RF). Loop 1 = built-in shock sensor Loop 2 = built-in magnetic reed switch Loop 3 = externally wired, closed-circuit contact

UNIT DIMENSIONS
4.8" H x 1.5" W x 1" D

Regular maintenance and inspection (at least annually) by the installer and frequent testing by the user are vital to continuous satisfactory operation of any alarm system. The installer should assume the responsibility of developing and offering a regular maintenance program to the user, as well as acquainting the user with the proper operation and limitations of the alarm system and its component parts. Recommendations must be included for a specific program of frequent testing (at least weekly) to ensure the system's operation at all times. REFER TO THE INSTALLATION AND SETUP GUIDE FOR THE CONTROL PANEL WITH WHICH THIS DEVICE IS USED FOR WARRANTY INFORMATION, AND FOR DETAILS REGARDING THE LIMITATIONS OF THE ENTIRE ALARM SYSTEM.

TO THE INSTALLER

FCC AND INDUSTRY CANADA STATEMENT This device complies with Part 15 of the FCC Rules and RSS210 of the Industry Canada. Operation is subject to the following two conditions: (1) This device may not cause harmful interference (2) This device must accept any interference received, including interference that may cause undesired operation. The user shall not make any changes or modifications to the equipment unless authorized by the Installation and Setup Guide or User Guide.

165 Eileen Way, Syosset, New York 11791
Copyright © 2005 Honeywell International Inc. www.honeywell.com/security

ÊN7491-1V2ÇŠ
N7491-1V2 6/06 Rev. A


Uploaded