Honeywell Vista 15p and Honeywell Vista 20p Quick Install Guide


Pete, the 4120TR (https://www.alarmgrid.com/products/honeywell-4120tr ) trigger cable should work for you.
My apologies, Pete. I was not aware we carried this item. Sorry for any inconvenience.
I am trying to locate the 4 wire trigger connector for a vista 20p p/n N4632-4 where should i be able to find one

Related Products

Honeywell VISTA-20P - Wired Alarm Control Panel
Honeywell VISTA-20P
Wired Alarm Control Panel
List Price: $244.00
Our Price: $150.99
Honeywell VISTA-15P - Alarm Control Panel
Honeywell VISTA-15P
Alarm Control Panel
List Price: $196.00
Our Price: $121.99
Honeywell Tuxedo Touch - Talking Color Graphic Touchscreen Alarm Keypad
Honeywell Tuxedo Touch
Talking Color Graphic Wired Touchscreen Alarm Keypad
Honeywell Tuxedo Touch WIFI - Talking Color Graphic Touchscreen Alarm Keypad
Honeywell Tuxedo Touch WIFI
Talking Color Graphic Touchscreen Alarm Keypad

Related Categories


Document Transcript

  (A copy of the Installation and Setup Guide is available upon request)
FOR DOCUMENTATION AND ONLINE SUPPORT: http://www.security.honeywell.com/hsc/resources/MyWebTech (see instructions K5305-1V9 or higher)

These instructions apply to the following Honeywell security systems: ADEMCO VISTA-20P, VISTA-20PSIA, VISTA-20PCN, VISTA-15P, VISTA-15PSIA, VISTA-15PCN Features and procedures apply to all, except where differences are noted. VISTA-20PSIA and VISTA-15PSIA are certified SIA-compliant controls that meet SIA specifications for False Alarm Reduction.

Mount the Control.
1. Remove the cabinet door. Remove the cabinet knockouts needed for wiring entry. 2. Mount the control cabinet to a sturdy wall in a clean, dry area, which is not readily accessible to the general public, using fasteners or anchors (not supplied) with the four cabinet mounting holes. 3. When installation and wiring is completed, install the cabinet door and secure by using 2 screws (supplied) through the door's edge. OPTIONAL KEY LOCK: If desired, a key lock can be installed (K4445, not supplied). See Installation Instructions for details.

Connect Devices, Zones, Sounder, and Phone Line.
Refer to the Wiring Diagram on the reverse side for connection information. NOTE: This system uses a range of reserved addresses for each type of device. 1. Connect keypads and other addressable devices to the ECP terminals 4-7. Relay Modules (4204) Refer to the wiring chart below for wire sizes and maximum wire run lengths. • Connect desired field wiring to the module’s relay contact terminals. Wire Chart For Devices Drawing Aux Power From The Control (12V+ & 12V–) • Relay module addresses range from address 12-15.Set each module’s DIP address accordingly. Wire TOTAL CURRENT OF ALL DEVICES CONNECTED TO A SINGLE WIRE RUN • Use ∗79 / ∗80 Menu modes to map each device address and define output functions. Size 50 mA or less 100 mA 300 mA 500 mA 600 mA Communication Device (7847i, 7845GSM, 7845i-GSM, GSMV) #22 900ft (274m) 450ft (137m) 150ft (46m) 90ft (27m) 75ft (23m) • Set the communication device to address 03. #20 1400ft (427m) 700ft (213m) 240ft (73m) 140ft (43m) 120ft (37m) • Use ∗29 Menu mode to enable and program the device. #18 1500ft (457m) 1100ft (335m) 350ft (107m) 220ft (67m) 170ft (52m) AVS System #16 1500ft (457m) 1500ft (457m) 550ft (168m) 350ft (107m) 270ft (82m) • If used, follow the installation instructions provided with the module. The length of all wire runs for both partitions combined must not exceed 1500 feet (457m) when unshielded quad • Connect the AVS module to the control’s ECP terminals and connect all other ECP devices to the conductor cable is used (750 feet if shielded cable is used). AVS module’s ECP terminals. Standard Keypads (6150 / 6160 series) • Set the AVS address using its DIP switches: V15P = 08; V20P = 11 • Keypad addresses range from address 16-23. Set each keypad’s address accordingly. • Use the desired AVS Quick Program Command to set pre-defined options: NOTE: Address 16 is reserved for the first keypad and is always enabled in the control. installer code + [#] + 0 + 3: enable AVS operation • Use data fields ∗190-∗196 to enable keypads and set their sounding options. installer code + [#] + 0 + 4: enable AVS and enable panel sounds on AVST speaker Expander Modules (4219, 4229) • Use field ∗55 Dynamic Signaling Priority to select the desired reporting paths. • Connect desired field wiring to the module’s zone terminals. 2. Connect hardwire zones to the appropriate zone terminals 8-20. • Expander module addresses range from 07-11. Set each module’s DIP address accordingly. 3. On-Board Trigger Connections • Use ∗56 Menu mode to program zone characteristics. • Connect field wiring to the appropriate trigger pin using the SA4120XM-1 cable (if using 1361X10 Touchscreen Keypads (6270 / 6271 series, 8132 series; V20P = up to 4; V15P = up to 2) transformer) or the 4-wire cable (N4632-4, not supplied). • Use of touchscreen keypads is independent from and in addition to the eight (8) standard keypads. • Trigger outputs are normally high, and go low upon programmed condition (can be set inverted). • Set each touchscreen’s address accordingly (1, 2, 5, 6; see table on back) and enable in field ∗189. • Use ∗79/∗80 Menu modes to program the trigger outputs. • Make sure the auxiliary current drain is within the control’s limitation. Otherwise use an external • Output 17 (pin 1) = supports up to 100mA max; Output 18 (pin 5) = supports up to 20mA max power supply to power the touchscreen keypads. RF Receiver (5881, 5883, RF Keypad) • 5881L / 5882L = up to 8 RF zones; 5881M / 5882M / 6150RF = up to 16 RF zones 5881H / 5882H / 5883 / 6160RF = up to system maximum RF zones • Set the receiver’s address to 00 using the module’s DIP switches. • If using wireless keypads, set field ∗24 RF House ID Code appropriately. If receiver is mounted remotely, note the following: • Do not locate the receiver or transmitters on or near metal objects. This will decrease range and/or block transmissions. • Do not locate the RF receiver in an area of high RF interference (indicated by frequent or prolonged lighting of the receiver’s LED; random flicker is OK). • Do not locate RF receiver closer than 10 feet from any keypads. 4. Install Wireless Zone Transmitters. • Use ∗56 Menu mode to program wireless zones and enroll the transmitters. • Use the Go/No Go Test mode to verify adequate signal strength from each transmitter location: Enter Installer code + [#] + 4, then fault each transmitter and listen for 3 beeps at the keypad and the zone display. Exit mode: user code + 1 (OFF). 5. Connect the external sounder to terminals 3 and 4. • If supervised output desired, see Sounder Supervision wiring diagram on reverse side, and set field ∗91 Option Selection for Bell Supervision. 6. Connect the phone line using terminals 21-24. • Use an RJ31X jack as shown in the diagram on reverse side.

SECURE WITH SCREWS (2)

cab_6a-V0

Securing the Cabinet Door 4. Mount the PC Board. Refer to the diagram below. If mounting an RF Receiver inside the cabinet, remove the receiver board from its case, then insert the top of the board into the slots at the top of the cabinet. Install the control board below the receiver board using the clips and screws provided. Insert grounding lugs into the left-hand terminals of the antenna blocks and secure them with the screws provided. Insert the receiver's antennas into the blocks' right-hand terminals, and tighten the screws.
CIRCUIT BOARD CABINET
+ +

CIRCUIT BOARD

CABINET

DETAIL A SIDE VIEW OF BOARD SUPPORTING SLOTS

DETAIL B SIDE VIEW OF MOUNTING CLIPS

INSERT THE TOP OF THE CIRCUIT BOARD INTO THE SLOTS AT THE TOP OF THE CABINET

HANG TWO SHORT MOUNTING CLIPS (PROVIDED) ON THE RAISED CABINET TABS. SECURE THE BOARD TO THE CABINET WITH THE ACCOMPANYING cb_mount-001-V1 SCREWS

Mounting the PC Board

Connect the Transformer & Battery.
1321 Transformer (1321CN in Canada) • Do not plug the transformer into the AC outlet until all wiring connections to the control are complete. As a safety precaution, always power down the control when making such connections. 1361X10 Transformer (required if using Powerline Carrier devices) 1. Splice one end of a 3-conductor cable to the wire ends of the SA4120XM-1 cable. 2. Connect the SA4120XM-1 cable plug to the 8-pin connector on the control. 3. Connect the other end of the 3-conductor cable to the 1361X10 Transformer. Canadian Installations: For Powerline Carrier Devices, use the PSC04 X-10 Interface and trigger pins. Battery Connections • After all connections to the control are completed and after AC power has been applied, connect the red and black flying leads on the control board to the battery. • IMPORTANT: This control will not power-up on battery alone (AC power must be applied). However, once the system is powered up, it will operate on battery if AC is lost. UL For UL installations and Residential fire installations, refer to the chart below for the correct battery size required to meet the mandatory standby time. CALIFORNIA STATE FIRE MARSHALL (CSFM) AND UL RESIDENTIAL FIRE 24-HOUR BATTERY BACKUP REQUIREMENTS The California State Fire Marshal and UL have regulations which require that all residential fire alarm control panels must be provided with a backup battery which has sufficient capacity to operate the panel and its attached peripheral devices for 24 hours in the intended standby condition, followed by at least 4 minutes in the intended fire alarm signaling condition. This control panel can meet these requirements without using a supplementary power supply, provided that the panel’s auxiliary power and bell output currents are limited as listed below. OUTPUT LIMITATIONS AND REQUIRED BATTERIES OUTPUT CURRENT LIMITS BATTERY INFORMATION Current Total Max. Aux.Current Battery Capacity (Amp/Hrs) Recommended Battery (Yuasa No.) 45mA 4AH NP4-12 (or ADEMCO 467) 600mA 160mA 7AH NP7-12 maximum total of 8AH 200mA NP4-12 (two) ‡ auxiliary power 14AH 425mA NP7-12 (two) ‡ plus bell output 17.2AH 500mA NPG18-12 currents ‡ NOTE: Use two batteries, connected in parallel. Obtain an Ademco Battery Harness Kit SA5140-1. (Both batteries will
fit inside the cabinet.)

Program the Control.
Refer to the Programming Guide to program the control. (The control can also be programmed via the Compass Downloader.) 1. Enter Programming Mode: installer code + 8-0-0. 2. Change the default Installer Code using field ∗20. 3. Enter the appropriate central station phone numbers and account numbers. 4. Program the system data field options as desired. 4. Use the various menu modes to program zones, relay outputs, descriptors, etc. 5. If AVS system is installed, use the appropriate AVS Quick Program Command. 6. Program Schedules (if used): Master code + [#] + 64 7. Enable RF button keyfobs (if used) and assign to user numbers accordingly. 8. Show the Master user how to change the default Master code: master code + [8] + 0-2 + new code + new code again

Major Features and Capacities
Feature Partitions Zones VISTA-20P 2 plus common area 48 plus 16 keyfob zones for total of 64 zones: • 8 hardwired zones (1-8) • Up to 40 additional wired zones (9-48) using up to 5 4219/4229 modules • Up to 40 wireless zones (5800 series; zones 9-48) • 4 configurable zone types Security Codes 48 Schedules 32 Keypad macros 4 Event Logging 100 Paging 4 Keypads 8 Touch Screen Devices 4 4219, 4229 5 4204 4 Output Relays / X-10 devices 16 On-Board Triggers 2 Output Functions 48

Test the System.
Sniffer Mode Test: To verify that all transmitters have been properly programmed, disarm all partitions. 1. From a keypad in partition 1, enter Installer code + [#] + 3. All programmed transmitters are displayed. 2. Fault all transmitters in turn. The display clears each transmitter as a signal is received. 3. Exit Sniffer mode: Installer code + 1 (OFF). Mode does not automatically expire; you must exit manually. System Test 1. Disarm the system and close all protected windows, doors, etc. 2. Enter the Installer code + [5] (TEST), then press 0 = walk. (Option 1 = Dial checks phone line integrity.) 3. Listen. The external sounder should sound for about 1 second then turn off. 4. Fault all zones in turn and listen for three beeps from the keypad. ID of each faulted point should appear on the keypad display. The display clears when the zone is restored. 5. Test all smoke and CO detectors following the manufacturer's instructions and check the display. 6. When all zones have been checked and are intact (closed), there should be no zone identification numbers displayed on the keypad. 7. Exit test mode: security code + [1] (OFF).

VISTA-15P not partitioned 32 zones plus 8 keyfob zones for total of 40 zones: • 6 hardwired zones (1-6) • Up to 16 additional wired zones (9-24) using up to 2 4219/4229 modules • Up to 26 wireless zones (5800 series; zones 9-34) • 2 configurable zone types 32 8 2 50 2 8 2 2 2 8 2 24

WARRANTY INFORMATION
For the latest warranty information, please go to: www.honeywell.com/security/hsc/resources/wa


K5305-1QGV3 2/11 Rev. A

2 Corporate Center Drive, Suite 100 P.O. Box 9040, Melville, NY 11747
Copyright © 2009 Honeywell International Inc. www.honeywell.com/security

AC POWERAC POWER CONNECTION AND BATTERY CONNECTION
TRANSFORMER 1. CONNECT THE TRANSFORMER TO TERMINALS 1 AND 2. SEE WIRE RUN CHART. TRANSFORMER WIRE RUNS USE CAUTION WHEN WIRING Distance from control Wire Size THE TRANSFORMER TO THE # 20 CONTROL TO GUARD AGAINST Up to 50 feet BLOWING THE TRANSFORMER 50 - 100 feet # 18 FUSE (THE FUSE IS 100 - 200 feet # 16 NON-REPLACEABLE). 2. AFTER ALL WIRING CONNECTIONS ARE COMPLETE, PLUG TRANSFORMER INTO A 110VAC UNSWITCHED OUTLET (24HR). USE 1361X10 TRANSFORMER INTERFACE WHEN POWER LINE CARRIER DEVICES ARE BEING USED. "AC LOSS" DISPLAYED IF VOLTAGE FALLS BELOW 16.5VAC. BATTERY 1. PLACE THE 12-VOLT BACKUP BATTERY IN THE CABINET. 2. AFTER ALL CONNECTIONS TO THE CONTROL ARE MADE AND AFTER AC POWER HAS BEEN APPLIED, CONNECT THE RED AND BLACK FLYING LEADS TO THE BATTERY. IMPORTANT: THE PANEL WILL NOT POWER UP INITIALLY ON BATTERY POWER ONLY. YOU MUST PLUG THE TRANSFORMER IN FIRST, AND THEN CONNECT THE BATTERY.

+12 AUX. (RED)

RED BLACK
OPTIONAL 1361X10

PROGRAM RELAY AS ZONE TYPE 54 (FIRE ZONE RESET)
N.C. CONTACT OPENS MOMENTARILY UPON FIRE ALARM RESET +
4-WIRE SMOKE OR COMBUSTION DETECTOR

BLK

+

RED EOL POWER SUPERVISION RELAY MODULE EOLR-1. USE N.O. CONTACT, WHICH CLOSES WHEN POWER IS APPLIED.

OUTPUT 18 (GRN)

OUTPUT 17 (YEL)

RECHARGABLE BATTERY (12V, 4AH) SEALED LEAD ACID TYPE

BATTERY FUSE (IF INSTALLED) FOR REPLACEMENT, 3A USE SAME VALUE CANADA: USE PSC04. (e.g. ADEMCO No. 90-12) SEE INSTALLATION INSTRUCTIONS. FUSE NOTE MAY HAVE PTC IN PLACE OF FUSE.

TRIGGER CONNECTOR USED FOR 1361X10 TRANSFORMER CONNECTIONS AND FOR ON-BOARD TRIGGERS. OUT 17 = 100mA MAX OUT 18 = 20mA MAX 1 2 3 4 5 6 7 8

4-WIRE SMOKE DETECTOR CONNECTIONS
+ 5

KEYSWITCH WIRING CONNECTIONS
1 2 3 4 5 6 7 8 TRIGGER CONNECTOR

AUX PWR OUTPUT TERMINALS

RELAY

4

UL: SEE INSTALLATION INSTRUCTIONS FOR USAGE AND LIMITATIONS.
4146 KEYSWITCH (ARMED) RED

N.O.

OUTPUT 17 (TRIG. 1)

GND

OUTPUT 18 (TRIG. 2)

+12 AUX

OR

UL: PLC DEVICES AND 1361X10 ARE NOT UL LISTED FOR FIRE OR BURGLARY FUNCTIONS AND ARE INTENDED FOR HOME AUTOMATION.

1321 (1321CN IN CANADA) 16.5VAC, 25VA, CLASS 2 PLUG-IN TRANSFORMER

TO TERMINALS 1&2

BLUE (DATA) PURPLE (COM) BLACK (SYNC) (USE SA4120XM-1 CABLE)

TO OUTPUT 17 PROGRAM OUTPUT 17 FOR "OUT NORM LOW" = YES IN 79 MENU MODE AND AS ZONE TYPE 54 IN 80 MENU MODE MAX. CURRENT = 100 mA

VIOLET

STANDARD KEYPAD CABLE YELLOW

2000 OHMS EOLR

(READY) GREEN WHITE

(+) TO ZONE 2 8 TERM. ( )

ECP AUX POWER OUTPUT
10.5-13.8VDC 600mA MAX. (500mA MAX. FOR UL INSTALLATIONS)
AC
1

HEAT DETECTOR

BLACK RED

820 ohms

820 ohms

HANDSET Z1+ Z1
8 9

INCOMING GND
25
11 TYPICAL ZONE ON CONTROL BOARD 10 BLUE BROWN

ECP DEVICES AC BELL GND AUX IN OUT
2 3 4 5 6 7

GND
10

Z2
11

HARDWIRE ZONES Z3 GND Z4 Z5 GND
12 13 14 15 16

TAMPER SWITCH (N. C.) BROWN

Z6
17

Z7
18

GND Z8
19 20

TIP RING TIP RING
21 22 23 24

LOCK SWITCH (N. O.) BLUE

LO

LO

LO

LO

LO

LO

LO

HI

HI

HI

HI

HI

HI

HI

GREEN

GRAY

RED

SOUNDER CONNECTION
RED

BROWN

SOUNDER ACTIVATES UPON ALARM EVENT. ALARM OUTPUT: 10.5–13.8VDC, 2A MAX. (600mA MAX. FOR UL USAGE, INCLUDING AUX POWER). STEADY FOR BURGLARY/PANIC. TEMPORAL PULSE SOUNDING FOR FIRE. UL: MUST BE A UL LISTED AUDIBLE SIGNAL APPLIANCE RATED FOR 10.2-13.8 VDC AND BE MOUNTED INDOORS. CAN USE ADEMCO No. 702 SIREN, OR 12V BELL. A BATTERY MUST BE INSTALLED BECAUSE THE BATTERY SUPPLIES THE SOUNDER CURRENT. FOR SOUNDER SUPERVISION
UL: BELL SUPERVISION IS REQUIRED FOR FIRE ALARM INSTALLTIONS. IF BELL SUPERVISION IS ENABLED ( 91 ENABLED) CONNECT AN 820 OHM RESISTOR ACROSS THE EXTERNAL SOUNDER AS SHOWN BY THE DOTTED LINE. EXTERNAL ALARM SOUNDER

YELLOW

CONNECT SOUNDER TO BELL TERMINALS 3 (+) AND 4 (-).
GREEN BLACK

EARTH GROUND
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ZONE 7 ZONE 8

2K OHM EOLR

4219/4229 EXPANDER MODULE

RF RECEIVER

EARTH GROUND CONNECTION
DIRECT CONNECT CORD (620)
THIS CONTROL DOES NOT NORMALLY NEED AN EARTH GROUND. IF DESIRED FOR ADDITIONAL PROTECTION, CONNECT TERMINAL 25 TO A GOOD EARTH GROUND. EXAMPLES OF GOOD EARTH GROUNDS: METAL COLD WATER PIPE: USE A NON-CORROSIVE METAL STRAP (COPPER IS RECOMMENDED) FIRMLY SECURED TO THE PIPE TO WHICH THE GROUND LEAD IS ELECTRICALLY CONNECTED AND SECURED. AC POWER OUTLET GROUND: AVAILABLE FROM 3-PRONG, 120VAC POWER OUTLETS ONLY. TO TEST THE INTEGRITY OF THE GROUND TERMINAL, USE A 3-WIRE CIRCUIT TESTER WITH NEON LAMP INDICATORS, SUCH AS THE UL LISTED IDEAL MODEL 61-035, OR EQUIVALENT, AVAILABLE AT MOST ELECTRICAL SUPPLY STORES. RING (GRAY) TIP (BROWN) PREMISES PHONES RING (RED)

2000 OHMS EOLR
2-WIRE SMOKE DETECTORS (16 MAX) OR STANDARD 2K EOLR

2000 OHMS EOLR

2000 OHMS EOLR

2000 OHMS EOLR

2000 OHMS EOLR

2000 OHMS EOLR

2000 OHMS EOLR

2000 OHMS EOLR

VISTA-20P ONLY

SENSORS (USE 1K EOLR) TOUCHSCREEN KEYPAD (SEE TOUCHSCREEN NOTE BELOW) COMMUNICATION DEVICE

HARDWIRE ZONE CONNECTION
1. OPEN CIRCUIT DEVICES CONNECT IN PARALLEL ACROSS THE LOOP; FOR EOLR ZONES, CONNECT THE EOLR ACROSS THE LOOP WIRES AT THE LAST DEVICE. 2. CLOSED CIRCUIT DEVICES CONNECT IN SERIES IN THE HIGH (+) SIDE OF THE LOOP; FOR EOLR ZONES, CONNECT THE EOLR IN SERIES FOLLOWING THE LAST DEVICE. EOLR NOTE: IF THE EOLR IS NOT AT THE END OF THE LOOP, THE ZONE IS NOT PROPERLY SUPERVISED AND THE SYSTEM MAY NOT RESPOND TO AN "OPEN" ON THE ZONE. UL NOTE: FOR UL COMMERCIAL BURGLARY ALARM INSTALLATIONS, USE EOLR ZONES. DOUBLE-BALANCED ZONE VISTA-20P ONLY
1
OF F

TERM 4 TERM 3
OBSERVE POLARITY

820 OHM EOL RESISTOR

1

2

3

DO NOT CONNECT THE RESISTOR DIRECTLY TO THE ALARM OUTPUT TERMINALS!

RJ31X
8 7 6

RF RECEIVERS & TRANSMITTERS
CONTROLLED DEVICES

4 5 TIP GREEN)

INCOMING TELCO

SETTING KEYPAD ADDRESS
HOLD DOWN THREE SECONDS

4204 RELAY MODULE

AR

MED

ZONE DOUBLING VISTA-20P ONLY
PROVIDES TWO HARDWIRED N.C. ZONES FOR EACH STANDARD HW ZONE (BUT DOES NOT INCREASE TOTAL NUMBER OF ZONES SUPPORTED). A SHORT ACROSS THE EOL ON EITHER ZONE CAUSES A TAMPER CONDITION. ZONE NUMBERS USED FOR DOUBLING CANNOT BE USED FOR ANYTHING ELSE.

RE

AD

Y

4
MA X

2
AW AY

7
INS TAN T RE AD Y

5
TE ST

3
ST AY

8
CO DE

6 9 #

BY

PA

SS

0

CH

1. SET RECEIVER DEVICE ADDRESS TO "00" (SET SWITCHES TO THE RIGHT, "OFF" POSITION). 2. MOUNT THE RECEIVER INSIDE THE CABINET OR REMOTELY WITHIN A NOMINAL RANGE OF 200 FEET FROM TRANSMITTERS, IN A HIGH, CENTRALLY LOCATED AREA. 3. CONNECT THE RECEIVER'S WIRE HARNESS TO THE CONTROL'S ECP TERMINALS. SEE RECEIVER'S INSTRUCTIONS FOR ANTENNA MOUNTING, ETC. 4. INSTALL TRANSMITTERS ACCORDING TO THEIR INSTRUCTIONS. WIRELESS ZONE NUMBERS VISTA-20P VISTA-15P 40 TRANSMITTER ZONES: 9-48 26 TRANSMITTER ZONES: 9-34 16 BUTTON ZONES: 49-64 8 BUTTON ZONES: 49-56 ULC NOTE: THE RF SUPERVISION PERIOD FOR THE V20PCN AND V15PCN IS THREE HOURS FOR FIRE ZONES (ZT 9 AND 16) AND 12 HOURS FOR ALL OTHER ZONE TYPES.

IME

BLACK RED GREEN YELLOW

PROVIDES ZONE TAMPER PROTECTION AND SHOULD BE USED AS BURGLARY ZONES ONLY. A SHORT ACROSS THE EOL CAUSES A TAMPER CONDITION.

PHONE CONNECTION
1. CONNECT PHONE LINE DIRECT CONNECT CABLE WIRES TO TERMINALS 21-24 AS SHOWN. WIRE COLORS REPRESENT THE COLORS OF THE CABLE TO THE RJ31X JACK. 2. CONNECT INCOMING PHONE LINE AND HANDSET WIRING TO THE MAIN TERMINAL BLOCK (VIA AN RJ31X JACK; CA38A IN CANADA) AS SHOWN.
ARMED

1 4 7

OFF

2 5 8 0

AWAY

3 6 9 #

STAY

READY

MAX

TEST

BYPASS

KEYPAD

INSTANT

CODE

CHIME

12

13

14

READY

KEYPADS AND ADDRESSABLE DEVICE CONNECTION
1. CONNECT KEYPADS AND OTHER ADDRESSABLE DEVICES TO ECP TERMINALS 4-7. (SEE "SETTING KEYPAD ADDRESS" BOX TO SET KEYPAD ADDRESSES.) TOUCHSCREEN NOTE: TOUCHSCREEN KEYPADS MAY REQUIRE AN EXTERNAL POWER SUPPLY DUE TO AUX POWER LIMITATIONS. 2. SET EACH MODULE'S ADDRESS ACCORDINGLY: DEVICE ADDRESS DEVICE KEYPADS 4219, 4229 4204 RF RECEIVER 16 - 23 07 - 11 12 - 15 00 5800TM COMM DEVICE 4286 TOUCH SCREENS
2k 2k 2k 2k

ZONE PAIRS 10 ZONE 2 3k ZONE 10 6.2k 11 2 / 10 3 / 11 4 / 12 5 / 13 6 / 14 7 / 15 8 / 16

1. POWER UP THE KEYPAD. WITHIN 60 SECONDS OF POWER-UP, PRESS AND HOLD DOWN THE [1] & [3] KEYS AT THE SAME TIME FOR 3 SECONDS. 2. ENTER THE PROPER "TENS" DIGIT OF THE KEYPAD'S ADDRESS, THEN ENTER THE PROPER "ONES" DIGIT OF THE KEYPAD'S ADDRESS. NOTE: FIRST KEYPAD IS ADDRESS 16 3. PRESS [ ] TO SAVE THE DISPLAYED ADDRESS AND EXIT ADDRESS MODE.
V15P_V20P_quick-guide_CL

ADDRESS 28 (PART. 1 ONLY) 03 04 V15P: 1, 2 V20P: 1, 2, 5, 6
2k ZONE 3 2k ZONE 4

RESISTORS NOT SUPPLIED

DO NOT USE DOUBLE-BALANCED ZONES OR ZONE DOUBLING FOR FIRE ZONES.


Uploaded