System Sensor RRS-MOD for 2-Wire i3™ Smokes on a VISTA-20P Panel



Related Products

System Sensor RRS-MOD - Reversing Polarity and Synchronization Module
System Sensor RRS-MOD
Reversing Polarity and Synchronization Module
List Price: $124.00
Our Price: $87.99
Honeywell VISTA-21iPLTE-Res - Internet Alarm Control Panel
Honeywell VISTA-21iPLTE
Internet Alarm Control Panel
List Price: $392.00
Our Price: $242.99
Honeywell VISTA-20P - Wired Alarm Control Panel
Honeywell VISTA-20P
Wired Alarm Control Panel
List Price: $244.00
Our Price: $150.99
Honeywell VISTA-20PSIA - Alarm Control Panel
Honeywell VISTA-20PSIA
Alarm Control Panel
List Price: $244.00
Our Price: $150.99
Honeywell VISTA-20P-6160KT - VISTA-20P Alarm System with 6160 Alphanumeric Keypad
Honeywell VISTA-20P-6160KT
VISTA-20P Alarm System with 6160 Alphanumeric Keypad
List Price: $460.00
Our Price: $283.99
Honeywell VISTA-15PSIA - Alarm Control Panel
Honeywell VISTA-15PSIA
Alarm Control Panel
List Price: $196.00
Our Price: $121.99
Honeywell VISTA-15P - Alarm Control Panel
Honeywell VISTA-15P
Alarm Control Panel
List Price: $196.00
Our Price: $121.99

Document Transcript

-
1

-
Step
-by-Step


Tech Support

Updated 10/6/11

Vista-20P / FA168C Family w/RRS-Mod & 2-
wire Smokes

When using the RRS
-Mod and the S
ystem
Sensor 2wta
-b smoke detectors, we have found that the pulsing
relay
(RRS
-Mod)
will cause multiple fire signals
to report to the central station
. To prevent this issue we have to program
the
fire zone differently
using a configurable zone type
rather than a zt of 09 or 16. See Below for the complete
programming changes with their explanations:

Definition:

Configurable Zone Type –
this is a zone type that you can create
to fit
your application. In our application we need
to prevent the multiple reports. W
e will create a Custom Zone type disabling Auto Restore
to
do
this.

Programming
our Configurable Zone Type:
The table below can be found on a worksheet defined in the installation instructions.

ENTRY 1

ENTRY 2

ENTRY 7

ENTRY 8

Response when system is disarmed and zone is:

Auto
Restore

Vent
Zone

Display Faults

Power Rest/
Verification

Use Entry
Delay

1/2

Use Exit
Delay

Respond as
Interior Type

Intact EOL

Open

Sho
rted

0 = Normal

0 = Normal

0 = Normal

0 = no

0 = no

0 = show alarms
when armed &
disarmed

0 = No

0 =No

0 = No

0 = No

1 = Alarm

4 = Alarm

1 = Alarm

1 = yes

1 = yes

4 = power
reset after fault
(by code +
OFF)

1 = Delay 1

4 = use
exit delay

8 =
Yes

2 = Trouble

8 = Trouble

2 = Trouble

2 = Delay 2

3 = Fault

12 = Fault

3 = Fault

1 = don't show
alarms when armed
(show alarms,
troubles, faults
when disarmed
3 = never show any
alarms, troubles,
faults

Entry 1 = 0
+ 8 =
8

Entry 2 = 1 + 0 + 0 =
1

12 =
verification
(see zone type
16)

ENTRY 3

ENTRY 4

Response when system is STAY and zone is:

Byp.
when

Byp.
when

Intact EOL

Open

Shorted

disarmed

armed

0 = Normal

0
= Normal

0 = Normal

0 = no

0 = no

Entry 7 = 0 + 4 =
4

Entry 8 = 0 + 0 + 0 =
0

1 = Alarm

4 = Alarm

1 = Alarm

1 = yes

1 = yes

2 = Trouble

8 = Trouble

2 = Trouble

3 = Fault

12 = Fault

3 = Fault

Entry 3 = 0 + 8 =
8

Entry 4 = 1 + 0 + 0 =
1

E
NTRY 9

E
NTRY
10
Alarm Sounds

Use Bell Time
out

Respond
as Fire
Zone

Trouble
Sounds

Chime when
Chime Mode
On

ENTRY 5

ENTRY 6

Response when system is AWAY and zone is:

Dial
Delay

Fault
Delay

0

= none

0 = No
0 = No
0 = None

0 = No

Intact EOL

Open

Shorted

1 = Steady Keypad

4 = Yes

8 = Yes

1 =
Periodic
beep

4 = Yes

0 = Normal

0 = Normal

0 = Normal

0 = no

0 = no

2 = Steady bell and
keypad
1 = Alarm

4 = Alarm

1 = Alarm

1 = yes

1 = yes

see fields *32,
*33
See ZT 0
9
2 =
Trouble
beeps
2 = Trouble

8 = Trouble

2 = Trouble

3 = pulsing bell and
keypad

3 = Fault

12 = Fault

3 = Fault

Entry
5 = 0 + 8 =
8

Entry
6 = 1 + 0 + 0 =
1

Entry 9 = 3 + 4 + 8 =
15

Entry 10 = 2 + 0 =
2
N
ow that we have defined the configurable zone type,
we need to program the panel. There are up to 4 configurable
zone types, 90, 91, 92, 93. We are going to add the final values to *182
(zone type 90)
. To enter the data
press:

*182 -
8 1 8 1 8 1 4 0 #15 2
W
e also w
ant
to program the panel to send the same report
code
as a ZT of 09
. This
is CID of 110 for an Alarm and
373 for a
T rouble (refer to the installation instructions for a list of CID codes). This is programmed in location
*183. To enter this press the following command: *183 -
110 373. -
2

-
Step
-by-Step


Tech Support

Updated 10/6/11

When programming zone
1
through the control panel you will enter a value of 90 for the zone type:


















The


represents pressing the * (star) key

S
etting up through the compass software:

C
onfiguring the ZT:

U
sing Additional F
ire Zones:


I
f you have another fire zone, or are using Keypad Fire Panic, these also will trip the RRS
-MOD which is
wired to zone 1.

T
he pulsing RRS
-MOD,
without a latched smoke
detector
, will cause rapid Trouble/Restore reporting to
C.S.
When the RRS
-M
OD starts to pulse in conjunction with the bell output, the zone will report to the
panel a trouble on an open then a restore on close,
and will do this for the duration of the sounder. The
logic of the panel tells the dialer to report every T
rouble and e
very
Restore. This means
every time it
pulses it sends a signal to the dialer queue
, caus
ing
multiple
Trouble reports to be sent to C
entral
Station.

T
o prevent these repeat Trouble
reports when other Fire Zones are tripped, you
can
wire one of the trigge
rs
to the positive side of Zone 1
, and
program
the
trigger to activate upon “Alarm” of these other zones in
a
Z
one List. When one of these zones trip, the trigger will hold a short to ground on Z
one 1
, putting it into
Trouble
and preventing it from responding to the pulsing of the RRS
-MOD.
The different potentia
l
b
etween Zone 1 negative and Trigger negative causes trouble on the zone, not Alarm.

Enter Zn Num.

(00=Quit)

00
ZN ZT P RC IN: L

01 90 1 10 EL

01 Response Time

1
01 Report Code

1
st
01
2
nd
00
10
01 Partition

1
01 Zone Type

Config ZTYP1

90
ZN ZT P RC IN: L

01 09 1 10 EL

Enter Zn Num.

(00=Quit)

01 -
3

-
Step
-by-Step


Tech Support

Updated 10/6/11

See below for the wiring diagram.

The above schematic explains the wiring configuration. Now we have to program the panel to activate the trigger
17 (as shown above) when any zone exc
ept zone 1
is in
Fire
Alarm.
The Compass Screen Shots are found under the
Relay/X10 Tab.

*7
9 Programming:





Enter Output No.

00 = QUIT

00
17 Out Normal Low?

0=No, 1=Yes

0
Enter Output No.

00 = QUIT

17
Trigger 1 = Output # 17

Trigger
2 = Output # 18

DO NOT INSTALL HE
AT DETECTORS OR
PULL STATIONS ON THE SAME ZONE AS 2
-
WIRE SMOKES WHEN USING THE RRS
-MOD!

The

Jumper is ONLY to be used when you have
more than one Fire zone, including a keypad panic.



-
4

-
Step
-by-Step


Tech Support

Updated 10/6/11

*80 Programming:

































*8
1 Programming:








If zone 1 is entered in this Zone List it will cause the LED of the Smokes on Zone 1 not to
Latch on Alarm!
01 Enter Zn Num.

(00 = Quit)

00
01 Enter Zn Num.

(00 = Quit)

95
01 Enter Zn Num.

(00 = Quit)

02
Zone list No.

(00 = Quit)

01
Output Funct. #

(00 = Quit)

00
Output Funct. #

(00 = Quit)

00
Output #?

17
01 Output Action

Off

0
02 Enter Zone Type

Disarming

22
02 Activated by:

Zone Type

2
02 A E P Trig

?00 0 0 -
ZL=1

Output Funct. #

(00 = Quit)

02
Output #?

17
01 Output Action

Stay Closed

02
Enter Event

Alarm

1
01 Zone List

01
01 Activated by:

Zone List

1
01 A E P Trig

?00 0 0 -
ZL=1

Output Funct. #

(00 = Quit)

01


Uploaded